38 • Vacon apfiff09 marineTel. +35856. MARINE APPLICATION PARAMETER LIST6.1 Basic parametersCode Parameter Min Max Unit Default Cust ID NoteP2.1.1 Minimum frequency 0,00 P2.1.2 Hz 0,00 101P2.1.2 Maximum frequency P2.1.1 320,00 Hz 50,00 102NOTE: If fmax > than themotor synchronous speed,check suitability for motorand drive systemP2.1.3 Motor nominalvoltage 180 690 VNX2: 230VNX5: 400VNX6: 690V110Check the rating plate ofthe motor. Note also usedconnection Delta/StarP2.1.4 Motor nominalfrequency 8,00 320,00 Hz 50,00 111 Check the rating plate ofthe motorP2.1.5 Motor nominalspeed 5 20 000 rpm 1440 112The default applies for a 4-pole motor and a nominalsize frequency converter.P2.1.6 Motor nominalcurrent 0,1 x IH 2 x IH A IH 113 Check the rating plate ofthe motor.P2.1.7 Motor cos 0,30 1,00 0,85 120 Check the rating plate ofthe motorP2.1.8 Motor NominalPower 0,0 3200,0 kW 0,0 116 Check the rating plate ofthe motorP2.1.9 Magnetizing current 0,00 100,00 A 0,00 6120,00 A = Drive usesestimated value frommotor name plate valuesP2.1.10 Identification 0 4 0 6310=No action1=Identification w/o run2=Identification with run3=Encoder ID Run4=Ident All5=Absolute encoder,locked rotorNOTE: Set motor controlmode to Freq Controlbefore identification!P2.1.11 Motor type 0 1 0 650 0=Induction Motor1=PMS MotorTable 6-1. Basic parameters G2.1