apfiff09 marine vacon • 4324-hour support +358 (056.4 Input Signals6.4.1 Basic SettingsCode Parameter Min Max Unit Default Cust ID NoteP2.4.1.1 Start/Stop logicselection 0 7 0 300Startsignal 1(Default:DIN1)Startsignal 2(Default:DIN2)01234567Start fwdStart/StopStart/StopStart pulseStartStart fwd*Start*/StopStart*/StopStart rvsReverseRun enableStop pulseMot.Pot UPStart rvs*ReverseRun EnableTable 6-5. Input signals: basic settings, G2.2.16.4.2 Digital inputsCode Parameter Min Default Cust ID NoteP2.4.2.1 Start signal 1 0.1 A.1 403 Forward, See ID300P2.4.2.2 Start signal 2 0.1 A.2 404 Reverse. See ID300P2.4.2.3 Run enable 0.1 0.2 407 Motor start enabled (cc)P2.4.2.4 Reverse 0.1 0.1 412 Direction forward (oc)Direction reverse (cc)P2.4.2.5 Preset speed 1 0.1 0.1 419 See preset speeds in basingparameter group G2.1P2.4.2.6 Preset speed 2 0.1 0.1 420P2.4.2.7 Preset speed 3 0.1 0.1 421P2.4.2.8 Motor potentiometerreference DOWN 0.1 0.1 417 Mot.pot. reference decreases (cc)P2.4.2.9 Motor potentiometerreference UP 0.1 0.1 418 Mot.pot. reference increases (cc)P2.4.2.10 Fault reset 0.1 0.1 414 All faults reset (cc)P2.4.2.11 External fault (close) 0.1 0.1 405 Ext. fault displayed (cc)P2.4.2.12 External fault (open) 0.1 0.2 406 Ext. fault displayed (oc)P2.4.2.13 Acc/Dec time selection 0.1 0.1 408 Acc/Dec time 1 (oc)Acc/Dec time 2 (cc)P2.4.2.14 Acc/Dec prohibit 0.1 0.1 415 Acc/Dec prohibited (cc)P2.4.2.15 DC braking 0.1 0.1 416 DC braking active (cc)P2.4.2.16 Jogging speed 0.1 0.1 413 Jogging speed selected forfrequency reference (cc)P2.4.2.17 IO reference 1 / 2 selection 0.1 0.1 422 IO reference selection:14 ID117P2.4.2.18 Control from I/O terminal 0.1 0.1 409 Force control place to I/O terminal(cc)P2.4.2.19 Control from keypad 0.1 0.1 410 Force control place to keypad (cc)P2.4.2.20 Control from fieldbus 0.1 0.1 411 Force control place to fieldbus(cc)P2.4.2.21 Parameter set 1/set 2selection 0.1 0.1 496 Closed cont.=Set 2 is usedOpen cont.=Set 1 is usedP2.4.2.22 Motor control mode 1/2 0.1 0.1 164Closed cont.=Mode 2 is usedOpen cont.=Mode 1 is usedSee par 2.6.1, 2.6.12P2.4.2.23 External BrakeAcknowledge 0.1 0.2 1210 Monitoring signal frommechanical brakeP2.4.2.24 Cooling Monitor 0.1 0.2 750 Used when water cooled unitP2.4.2.25 Enable Inching 0.1 0.1 532 Enables Inching function* = Rising edge required to start