A.4 b: ApplicationApplication parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PIcontrol, Energy Savings, and a variety of other application-related settings.u b1: Operation Mode SelectionNo.(Addr.Hex) Name LCD Display Description Values Pageb1-01(180)Frequency ReferenceSelection for AUTOmodeRef Source 10: Operator1: Analog Input2: Serial Com3: Option PCB0: HOA keypad1: Terminals (Analog Input Terminals)2: Serial communications (APOGEE FLN, BACnet,MEMOBUS/Modbus, or Metasys N2)3: Option cardDefault: 1Range: 0 to 3 24b1-02(181)Run CommandSelection for AUTOmodeRun Source 11: Digital Inputs2: Communication3: Option PCB1: Control Circuit Terminal2: Serial communications (APOGEE FLN, BACnet,MEMOBUS/Modbus, or Metasys N2)3: Option cardDefault: 1Range: 1 to 3 25b1-03(182) Stopping MethodSelectionStopping Method0: Ramp to Stop1: Coast to Stop2: DCInj to Stop3: Coast w/Timer0: Ramp to stop1: Coast to stop2: DC Injection Braking to stop3: Coast with timerDefault: 1Range: 0 to 3 26b1-04(183) Reverse OperationSelectionReverse Oper0: Reverse Enabled1: Reverse Disabled0: Reverse enabled1: Reverse disabled Default: 1Range: 0, 1 28b1-08(187)Run CommandSelection inProgramming ModeRUN dur PRG Mode0: RunDisabled@PRG1: ModeRunEnabled@PRG2: Prg only @ Stop0: Run command is not accepted while in Programming Mode1: Run command is accepted while in Programming2: Prohibit entering Programming Mode during Run Default: 0Range: 0 to 2 28b1-11(1DF) Drive Delay TimeSetting Run Delay Time After a Run command is entered, the drive output waits untilthis delay time has passed before starting. Default: 0 sMin.: 0Max.: 600 28b1-14(1C3) Phase Order Selection Rotation Sel0: Standard1: SwitchPhaseOrder0: Standard1: Switch phase order (reverses the direction of the motor) Default: 0Range: 0, 1 28b1-17(1C6) Run Command at PowerUpRun Cmd @ Pwr On0: Cycle Ext Run1: Accept Ext Run0: Disregarded.A new Run command must be issued after power up.1: Allowed.Motor will start immediately after power up if a Run commandis already enabled.Default: 1Range: 0, 1 29u b2: DC Injection Braking and Short Circuit BrakingNo.(Addr.Hex) Name LCD Display Description Values Pageb2-01(189) DC Injection BrakingStart Frequency DCInj Start FreqSets the frequency at which DC Injection Braking starts when“Ramp to stop” (b1-03 = 0) is selected. Default: <1>Min.: 0.0 HzMax.: 10.0 Hz29b2-02(18A) DC Injection BrakingCurrent DCInj Current Sets the DC Injection Braking current as a percentage of thedrive rated current. Default: 50%Min.: 0Max.: 100 30b2-03(18B) DC Injection BrakingTime at Start DCInj Time@Start Sets DC Injection Braking time at start. Disabled when set to0.00 seconds. Default: 0.00 sMin.: 0.00Max.: 10.00 30b2-04(18C) DC Injection BrakingTime at Stop DCInj Time@Stop Sets DC Injection Braking time at stop. Default: 0.00 sMin.: 0.00Max.: 10.00 30b2-09(1E1) Motor Pre-Heat Current2 Preheat Current Determines the percentage of motor rated output current usedfor the motor pre-heat function. Default: 5%Min.: 0Max.: 100 30A.4 b: ApplicationYASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual 187A Parameter List