A.9 H Parameters: Multi-Function TerminalsH parameters assign functions to the multi-function input and output terminals.u H1: Multi-Function Digital InputsNo.(Addr.Hex) Name LCD Display Description Values PageH1-01(438)Multi-Function DigitalInput Terminal S1Function Selection Term S1 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 204 to 207 for descriptions of setting values.Note: Set unused terminals to F.Default: 40 (F)<1>Min.: 1Max.: B272H1-02(439)Multi-Function DigitalInput Terminal S2Function Selection Term S2 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 204 to 207 for descriptions of setting values.Note: Set unused terminals to F.Default: 41 (F)<1>Min.: 1Max.: B272H1-03(400)Multi-Function DigitalInput Terminal S3Function Selection Term S3 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 204 to 207 for descriptions of setting values.Note: Set unused terminals to F.Default: 24Min.: 0Max.: B2 72H1-04(401)Multi-Function DigitalInput Terminal S4Function Selection Term S4 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 204 to 207 for descriptions of setting values.Note: Set unused terminals to F.Default: 14Min.: 0Max.: B2 72H1-05(402)Multi-Function DigitalInput Terminal S5Function Selection Term S5 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 204 to 207 for descriptions of setting values.Note: Set unused terminals to F.Default: 3 (0) <1>Min.: 0Max.: B272H1-06(403)Multi-Function DigitalInput Terminal S6Function Selection Term S6 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 204 to 207 for descriptions of setting values.Note: Set unused terminals to F.Default: 4 (3) <1>Min.: 0Max.: B272H1-07(404)Multi-Function DigitalInput Terminal S7Function Selection Term S7 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 204 to 207 for descriptions of setting values.Note: Set unused terminals to F.Default: 6 (4) <1>Min.: 0Max.: B272<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).H1 Multi-Function Digital Input SelectionsH1-ooSetting Function LCD Display Description Page0 3-Wire sequence 3-Wire Control Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)Terminals S1 and S2 are automatically set up for the Run command and Stopcommand. 733 Multi-Step SpeedReference 1 Multi-Step Ref 1 When input terminals are set to Multi-Step Speed References 1 through 3,switching combinations of those terminals will create a multi-step speed sequenceusing the frequency references set in d1-01 through d1-08.734 Multi-Step SpeedReference 2 Multi-Step Ref 2 When input terminals are set to Multi-Step Speed References 1 through 3,switching combinations of those terminals will create a multi-step speed sequenceusing the frequency references set in d1-01 through d1-08. 736 Jog reference selection jog Freq Ref Closed: Jog frequency reference (d1-17) selected. Jog has priority over all otherreference sources. 737 Accel/decel timeselection 1 Multi-Acc/Dec 1 Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/deceltime 2 (set in C1-03, C1-04). 748 Baseblock command(N.O.) Ext BaseBlk N.O. Closed: No drive output 749 Baseblock command(N.C.) Ext BaseBlk N.C. Open: No drive output 74A Accel/decel ramp hold Acc/Dec RampHold Open: Accel/decel is not heldClosed: The drive pauses during acceleration or deceleration and maintains theoutput frequency. 74B Drive overheat alarm(oH2) OH2 Alarm Signal An external device has triggered an oH2 alarm. 74C Analog terminal inputselection Term AI Enable Open: Function assigned by H3-14 is disabled.Closed: Function assigned by H3-14 is enabled. 74A.9 H Parameters: Multi-Function Terminals204 YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual