No.(Addr.Hex) Name LCD Display Description Values PageS3-16(3229) Secondary PI HighFeedback DetectionTime PI2 High FB TimSets the secondary PI high feedback detection delay time inseconds. Default: 1.0 sMin.: 0.0Max.: 25.5 143S3-17(322A) Secondary PI FeedbackDetection SelectionPI2 FB Det Sel0: PI2 Enabled1: Always0: Secondary PI enabled1: Always Default: 0Range: 0, 1 143<1> Unit is determined by S3-04.<2> Upper limit is S3-02, decimal placeholder is determined by S3-03.u S4: Bypass OperationNo.(Addr.Hex) Name LCD Display Description Values PageS4-01(322B) BP Auto Transfer onFault EnableBP Fault Trnsfer0: Disabled1: Enabled0: No transfer after fault1: Transfer to bypass after fault Default: 1Range: 0, 1 149S4-02(322C) BP Energy Save BypassTrigger Level BP Enrgy Sav Lvl Delta used to determine when to switch into Energy Save Bypass.This allows for lower frequency output values to also triggerEnergy Save Bypass functionality.Default: 0 HzMin.: 0Max.: 20 149S4-03(322D) BP Energy Save BypassTimer BP Enrgy Sav TMRSets the time in seconds that the drive should run at the specifiedspeed before entering Energy Save Bypass mode. Default: 60 sMin.: 10Max.: 60000 150S4-04(322E) BP Energy Save BypassSpeed Increase BP Enrgy Sav IncSets the value in Hz that the drive will increase the outputfrequency above E1-04 before performing an Energy Savetransfer to bypass.Default: 6 HzMin.: 0Max.: 10 150u S5: HOA Keypad ParametersNo.(Addr.Hex) Name LCD Display Description Values PageS5-01(322F) HAND FrequencyReference SelectionHAND Fref Source0: Operator1: Terminals2: d1-163: S5-054: Set by b1-010: HOA keypad1: Terminals2: d1-163: S5-054: Determined by b1-01Default: 0Range: 0 to 4 150S5-02(3230) HAND/AUTO DuringRun SelectionHAND/AUTO@Run0: Disabled1: Enabled0: Disabled1: Enabled Default: 1Range: 0, 1 150S5-03(3231) HAND Mode PISelectionHAND Mode PI Sel0: Disabled1: Enabled0: Disabled1: Enabled Default: 1Range: 0, 1 150S5-04(3232) HAND Mode BehaviorSelectionHAND BehaviorSel0: Legacy1: Normal2: Normal w/Memory0: Legacy operation mode1: Normal operation mode2: Normal with memoryNote: 1. The drive will always be in AUTO mode atpower up with S5-04 = 1.2. When S5-04 = 2, if the drive is powered downwith HAND from operator, it will power upin OFF mode.Default: 1Range: 0 to 2 150S5-05(3233) HAND FrequencyReference 1 HAND Freq Ref 2Sets the frequency reference used in HAND mode when S5-01is set to 3. Default: 0.00 HzMin.: 0.00Max.: 240.00 152A.13 S: Special Application228 YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual