1.7 H: Terminal FunctionsH parameters assign functions to the external terminals.u H1: Multi-Function Digital Inputsn H1-01 to H1-07: Functions for Terminals S1 to S7These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in Table1.28.No. Parameter Name SettingRange DefaultH1-01 Multi-Function Digital Input Terminal S1 Function Selection 1 to B2 40 (F) <1> : Forward Run Command (2-Wire sequence)H1-02 Multi-Function Digital Input Terminal S2 Function Selection 1 to B2 41 (F) <1> : Reverse Run Command (2-Wire sequence)H1-03 Multi-Function Digital Input Terminal S3 Function Selection 0 to B2 24: External FaultH1-04 Multi-Function Digital Input Terminal S4 Function Selection 0 to B2 14: Fault ResetH1-05 Multi-Function Digital Input Terminal S5 Function Selection 0 to B2 3 (0) <1> : Multi-Step Speed Reference 1H1-06 Multi-Function Digital Input Terminal S6 Function Selection 0 to B2 4 (3) <1> : Multi-Step Speed Reference 2H1-07 Multi-Function Digital Input Terminal S7 Function Selection 0 to B2 6 (4) <1> : Jog Reference Selection<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.Table 1.28 Multi-Function Digital Input Terminal SettingsSetting Function Page0 3-Wire Sequence 733 Multi-Step Speed Reference 1 734 Multi-Step Speed Reference 26 Jog reference Selection 737 Accel/Decel Time Selection 1 748 Baseblock Command (N.O.) 749 Baseblock Command (N.C.)A Accel/Decel Ramp Hold 74B Drive Overheat Alarm (oH2) 74C Analog Terminal Input Selection 74F Through Mode 7410 Up Command 7511 Down Command12 Forward Jog 7613 Reverse Jog14 Fault Reset 7615 Fast Stop (N.O.) 7617 Fast Stop (N.C.) 7618 Timer Function Input 7619 PID Disable 771B Program Lockout 771E Reference Sample Hold 7720 to 2F External Fault 7730 PID Integral Reset 7831 PID Integral Hold 7834 PID Soft Starter Cancel 7835 PID Input Level Selection 7840 Forward Run Command (2-Wire sequence) 7841 Reverse Run Command (2-Wire sequence)Setting Function Page42 Run Command (2-Wire sequence 2) 7843 FWD/REV Command (2-Wire sequence 2)44 Offset Frequency 17945 Offset Frequency 246 Offset Frequency 347 Node Setup 7949 GF1 Error (N.O., N.C.) 794A50 Motor Pre-Heat 2 7951 Sequence Timer Disable 7952 Sequence Timer Cancel 7960 Motor Pre-Heat 1 7961 External Speed Search Command 1 7962 External Speed Search Command 2 7963 Field Weakening 7965 KEB Ride-Thru 1 (N.C.) 8066 KEB Ride-Thru 1 (N.O.)67 Communications Test Mode 8068 High Slip Braking 8069 Jog 2 806A Drive Enabled 806D AUTO Mode Select 806E HAND Mode Select 8070 Drive Enable2 817A KEB Ride-Thru 2 (N.C.) 817B KEB Ride-Thru 2 (N.O.)7C Short Circuit Braking (N.O.) 817D Short Circuit Braking (N.C.)A4 Emergency Override 81A5 BP Drive/Bypass Selection 811.7 H: Terminal Functions72 YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual