u Metasys N2 Analog Output (AO) SummaryTable D.5 Metasys N2 Analog Output Summary (Z1000 to Metasys N2)Object ID Object Name Units Default Value Z1000 ParameterAO 1 Speed Command 0.01 Hz – –AO 2 Acceleration Time seconds 30.0 C1-01AO 3 Deceleration Time seconds 30.0 C1-02AO 4 PI Proportional Gain – 2.00 b5-02AO 5 PI Integral Time seconds 5.0 b5-03AO 6 Stall Prevention Level – Run % 120 L3-06AO 7 Stall Prevention Level – Accel % 120 L3-02AO 8 Reference Operation Mode Select – 1 b1-01AO 9 Run Operation Mode Select – 1 b1-02AO 10 PI Mode Select – 0 b5-01AO 11 Frequency Command Upper Limit % of Max 100.0 d2-01AO 12 Frequency Command Lower Limit % of Max 0.0 d2-02AO 13 Motor Rated Current A Motor model dependent E2-01AO 14 Jump Frequency 1 0.1 Hz 0.0 d3-01AO 15 Jump Frequency 2 0.1 Hz 0.0 d3-02AO 16 Jump Frequency 3 0.1 Hz 0.0 d3-03AO 17 Jump Frequency Bandwidth 0.1 Hz 1.0 d3-04AO 18 Number of Auto Restarts – 0 L5-01AO 19 Operator Display Mode – 0 o1-03AO 20 Power Loss Ride-Thru seconds Drive model dependent L2-02AO 21 Cable Loss Timeout seconds 2.0 H5-09AO 22 Cable Loss Speed 0.01 Hz 0.00 d1-04AO 23 PI Integral Limit 0.1% 100.0 b5-04AO 24 PI Upper Limit Value 0.1 100.0 b5-06AO 25 PI Offset Adjustment 0.1 0.0 b5-07AO 26 PI Primary Delay Time 0.01 0.00 b5-08AO 27 PI Feedback Reference MissingDetection Select 1 0 b5-12AO 28 PI Feedback Reference MissingDetection Level 1% 0 b5-13AO 29 PI Feedback Reference MissingDetection Time 0.1 s 1.0 b5-14AO 30 Read Parameter Number – – –AO 31 Write Parameter Number – – –AO 32 Write Parameter Data – – –u Metasys N2 Binary Input (BI) SummaryTable D.6 Metasys N2 Binary Input Summary (Z1000 to Metasys N2)Object ID Object Name Default Off (0) State On (1) StateBI 1 Run/Stop Monitor 0 Stopped RunningBI 2 Forward/Reverse Monitor 0 Forward ReverseBI 3 Drive Ready Monitor 0 Not Ready ReadyBI 4 Fault Monitor 0 Not Faulted FaultedBI 5 Zero Speed 0 Not Zero Speed Zero SpeedBI 6 Speed Agree 0 Not Speed Agree Speed AgreeBI 7 Minor Fault 0 No Minor Fault Minor FaultBI 8 Major Fault 0 No Major Fault Major FaultBI 9 Drive Communication Error Monitor 0 No Error ErrorD.7 Metasys N2 Point DatabaseYASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual 297D Metasys N2Communications