No.(Addr.Hex) Name LCD Display Description AnalogOutput Level UnitU1-12(4B) Drive Status Int Ctl Sts 1Verifies the drive operation status.U1 - 12=00000000 During runDuring zero-speedDuring REVDuring fault resetsignal inputDuring speed agreeDrive readyDuring alarmdetectionDuring fault detection11111111No signal outputavailable –U1-13(4E) Terminal A1 Input Level Term A1 Level Displays the signal level to analog input terminal A1. 10 V: 100% 0.1%U1-14(4F) Terminal A2 Input Level Term A2 Level Displays the signal level to analog input terminal A2. 10 V: 100% 0.1%U1-16(53) Output Frequency afterSoft Starter SFS Output Displays output frequency with ramp time and S-curves. Unitsdetermined by o1-03. 10 V: Maxfrequency 0.01 HzU1-18(61) oPE Fault Parameter OPE Error Code Displays the parameter number that caused the oPEoo or Err(EEPROM write error) error.No signal outputavailable –U1-19(66) MEMOBUS/ModbusError Code Transmit ErrDisplays the contents of a MEMOBUS/Modbus error.U1 - 19=00000000 CRC ErrorData Length ErrorNot UsedParity ErrorOverrun ErrorFraming ErrorTimed OutNot Used11011110No signal outputavailable –U1-25(4D) Software Number(Flash) CPU 1 SW Number FLASH ID No signal outputavailable –U1-26(5B) Software No. (ROM) CPU 2 SW Number ROM ID No signal outputavailable –U1-27(7A8) Message ID (OPR) MessageID (OPR) OPR ID No signal outputavailable –U1-28(7A9) Message ID (INV) MessageID (INV) INV ID No signal outputavailable –<1> Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.u U2: Fault TraceNo.(Addr.Hex) Name LCD Display Description AnalogOutput Level UnitU2-01(80) Current Fault Current Fault Displays the current fault. No signal outputavailable –U2-02(81) Previous Fault Last Fault Displays the previous fault. No signal outputavailable –U2-03(82) Frequency Reference atPrevious Fault Frequency Ref Displays the frequency reference at the previous fault. No signal outputavailable 0.01 HzU2-04(83) Output Frequency atPrevious Fault Output Freq Displays the output frequency at the previous fault. No signal outputavailable 0.01 HzU2-05(84) Output Current atPrevious Fault Output Current Displays the output current at the previous fault. No signal outputavailable <1> <2>A.15 U: MonitorsYASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual 233A Parameter List