No.(Addr.Hex) Name LCD Display Description Values PageS2-15(3214) Sequence Timer 3Reference SourceTmr 3 Ref Source0: Operator (d1-01)1: Operator (d1-02)2: Operator (d1-03)3: Operator (d1-04)4: Terminals5: Serial com6: Option PCBSelects the frequency reference source used for running the drivewhen sequence timer 3 is active (only applicable when S2-14 isset to 1 or 2).0: Operator (d1-01)1: Operator (d1-02)2: Operator (d1-03)3: Operator (d1-04)4: Terminals5: Serial communication6: Option cardNote: H1-oo = 12/13 overrides this sequence run timerin drive software versions PRG: 1018 and later.Default: 0Range: 0 to 6 139S2-16(3215) Sequence Timer 4 StartTime Tmr 4 Start Time Sets the start time for timer 4. The value must be set less than orequal to S2-17. Default: 00:00Min.: 00:00Max.: 24:00 138S2-17(3216) Sequence Timer 4 StopTime Tmr 4 Stop Time Sets the stop time for timer 4. The value must be set greater thanor equal to S2-16. Default: 00:00Min.: 00:00Max.: 24:00 138S2-18(3217) Sequence Timer 4 DaySelectionTmr 4 Day Sel0: Timer disabled1: Daily2: Mon - Fri3: Sat - Sun4: Monday5: Tuesday6: Wednesday7: Thursday8: Friday9: Saturday10: SundaySets the days for which sequence timer 4 is active.0: Timer disabled1: Daily2: Mon - Fri3: Sat - Sun4: Monday5: Tuesday6: Wednesday7: Thursday8: Friday9: Saturday10: SundayDefault: 0Range: 0 to 10 139S2-19(3218) Sequence Timer 4SelectionTmr 4 Seq Sel0: Digital out only1: Run2: Run - PI DisableSets the action that occurs when sequence timer 4 is active.0: Digital output only1: Run2: Run - PI disableDefault: 0Range: 0 to 2 139S2-20(3219) Sequence Timer 4Reference SourceTmr 4 Ref Source0: Operator (d1-01)1: Operator (d1-02)2: Operator (d1-03)3: Operator (d1-04)4: Terminals5: Serial com6: Option PCBSelects the frequency reference source used for running the drivewhen sequence timer 4 is active (only applicable when S2-19 isset to 1 or 2).0: Operator (d1-01)1: Operator (d1-02)2: Operator (d1-03)3: Operator (d1-04)4: Terminals5: Serial communication6: Option cardNote: H1-oo = 12/13 overrides this sequence run timerin drive software versions PRG: 1018 and later.Default: 0Range: 0 to 6 139u S3: Secondary PI (PI2) ControlNo.(Addr.Hex) Name LCD Display Description Values PageS3-01(321A) Secondary PI EnableSelectionPI2 Enable Sel0: Disabled1: Always2: Drive running3: Motor running0: Secondary PI disabled1: Always2: Drive running3: Motor runningDefault: 0Range: 0 to 3 140S3-02(321B) Secondary PI UserDisplay PI2 UsrDspMaxValSets the scale value of 100% PI input. Default: 10000Min.: 0Max.: 60000 140S3-03(321C) Secondary PI DisplayDigitsPI2 UsrDspDigits0: No Dec (XXXXX)1: 1 Dec (XXXX.X)2. 2 Dec (XXX.XX)3: 3 Dec (XX.XXX)0: No decimal places1: One decimal place2: Two decimal places3: Three decimal placesDefault: 2Range: 0 to 3 141A.13 S: Special Application226 YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual