u H2: Multi-Function Digital OutputsNo.(Addr.Hex) Name LCD Display Description Values PageH2-01(40B)Terminal M1-M2function selection(relay) M1-M2 Func Sel Refer to H2 Multi-Function Digital Output Settings on pages208 to 209 for descriptions of setting values. Default: 0Range: 0 to 1B2 82H2-02(40C)Terminal M3-M4function selection(relay) M3/M4 Func Sel Default: 1Range: 0 to 1B2 82H2-03(40D)Terminal M5-M6function selection(relay) M5/M6 Func Sel Default: 2Range: 0 to 1B2 82H2 Multi-Function Digital Output SettingsH2-ooSetting Function LCD Display Description Page0 During run During RUN 1 Closed: A Run command is active or voltage is output. 831 Zero speed Zero Speed Open: Output frequency is above the minimum output frequency set in E1-09.Closed: Output frequency is below the minimum output frequency set in E1-09. 832 Speed agree 1 Fref/Fout Agree1 Closed: Output frequency equals the speed reference (plus or minus the hysteresisset to L4-02). 843 User-set speed agree 1 Fref/Set Agree 1 Closed: Output frequency and speed reference equal L4-01 (plus or minus thehysteresis set to L4-02). 844 Frequency detection 1 Freq Detect 1 Closed: Output frequency is less than or equal to the value in L4-01 with hysteresisdetermined by L4-02. 845 Frequency detection 2 Freq Detect 2 Closed: Output frequency is greater than or equal to the value in L4-01 withhysteresis determined by L4-02. 856 Drive ready Drive Ready Closed: Power up is complete and the drive is ready to accept a Run command. 857 DC bus undervoltage DC Bus Undervolt Closed: DC bus voltage is below the Uv trip level set in L2-05. 868 During baseblock (N.O.) BaseBlk 1 Closed: Drive has entered the baseblock state (no output voltage). 869 Frequency referencesource Ref Source Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 orb1-15).Closed: HOA keypad supplies the frequency reference. 86A Run command source Run Cmd Source Open: External Reference 1 or 2 supplies the Run command (set in b1-02).Closed: HOA keypad supplies the Run command. 86B Torque detection 1(N.O.) Trq Det 1 N.O. Closed: An overtorque or undertorque situation has been detected. 86C Frequency reference loss Loss of Ref Closed: Analog frequency reference has been lost. 86E Fault Fault Closed: Fault occurred. 86F Through mode Not Used Set this value when using the terminal in the pass-through mode. 8610 Minor fault Minor Fault Closed: An alarm has been triggered, or the IGBTs have reached 90% of theirexpected life span. 8611 Fault reset commandactive Reset Cmd Active Closed: A command has been entered to clear a fault via the input terminals orfrom the serial network. 8712 Timer output Timer Output Closed: Timer output. 8713 Speed agree 2 Fref/Fout Agree2 Closed: When drive output frequency equals the frequency reference ±L4-04. 8714 User-set speed agree 2 Fref/Set Agree 2 Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04. 8715 Frequency detection 3 Freq Detect 3 Closed: When the drive output frequency is less than or equal to the value in L4-03±L4-04. 8816 Frequency detection 4 Freq Detect 4 Closed: When the output frequency is greater than or equal to the value in L4-03±L4-04. 8817 Torque detection 1(N.C.) Trq Det 1 N.C. Open: Overtorque or undertorque has been detected. 861A During Reverse Reverse Dir Closed: Drive is running in the reverse direction. 861B During baseblock (N.C.) BaseBlk 2 Open: Drive has entered the baseblock state (no output voltage). 891E Restart enabled Dur Flt Restart Closed: An automatic restart is performed 891F Motor overload alarm(oL1) Overload (OL1) Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggersthis alarm. 89A.9 H Parameters: Multi-Function Terminals208 YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual