u H5: MEMOBUS/Modbus Serial CommunicationNo.(Addr.Hex) Name LCD Display Description Values PageH5-01(425)<1> Drive Slave Address Serial Comm AdrSelects drive station slave number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S-. Cycle power for the settingto take effect.Default: 1F (Hex)Min.: 0Max.: FF 250H5-02(426) Communication SpeedSelectionSerial Baud Rate0: 1200 bps1: 2400 bps2: 4800 bps3: 9600 bps4: 19.2 kbps5: 38.4 kbps6: 57.6 kbps7: 76.8 kbps8: 115.2 kbps0: 1200 bps1: 2400 bps2: 4800 bps3: 9600 bps4: 19200 bps5: 38400 bps6: 57600 bps7: 76800 bps8: 115200 bpsCycle power for the setting to take effect.Default: 3Range: 0 to 8 250H5-03(427) Communication ParitySelectionSerial Com Sel0: No parity1: Even parity2: Odd parity0: No parity1: Even parity2: Odd parityCycle power for the setting to take effect.Default: 0Range: 0 to 2 250H5-04(428)Stopping Method afterCommunication Error(CE)Serial Fault Sel0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only4: Alarm(d1-04)0: Ramp to stop1: Coast to stop2: Fast Stop3: Alarm only4: Run at d1-04Default: 3Range: 0 to 4 251H5-05(429) Communication FaultDetection SelectionSerial Flt Dtct0: Disabled1: Enabled0: Disabled1: EnabledIf communication is lost for more than two seconds, a CE faultwill occur.Default: 1Range: 0, 1 251H5-06(42A) Drive Transmit WaitTime Transmit WaitTIM Set the wait time between receiving and sending data. Default: 5 msMin.: 5Max.: 65 251H5-07(42B) RTS Control Selection RTS Control Sel0: Disabled1: Enabled0: Disabled. RTS is always on.1: Enabled. RTS turns on only when sending. Default: 1Range: 0, 1 251H5-08(62D) CommunicationProtocol SelectionProtocol Select0: MEMOBUS1: N22: P13: BACnetSelects the communication protocol.0: MEMOBUS/Modbus1: N2 (Metasys)2: P1 (APOGEE FLN)3: BACnetDefault: 0Range: 0 to 3 251H5-09(435) CE Detection Time CE Detect Time Sets the time required to detect a communications error.Adjustment may be needed when networking several drives. Default: 2.0 sMin.: 0.0Max.: 10.0 252H5-10(436)Unit Selection forMEMOBUS/ModbusRegister 0025HCommReg 25h Unit0: 0.1 V1: 1 V0: 0.1 V units1: 1 V units Default: 0Range: 0, 1 252H5-11(43C)CommunicationsENTER FunctionSelectionEnter CommandSel0: Enter Required1: No EnterRequired0: Drive requires an Enter command before accepting anychanges to parameter settings.1: Parameter changes are activated immediately without theEnter command (same as V7).Default: 0Range: 0, 1 252H5-12(43D) Run Command MethodSelectionRun CommandSel0: FWD Run &REVRun1: Run & FWD/REV0: FWD/Stop, REV/Stop1: Run/Stop, FWD/REV Default: 0Range: 0, 1 252H5-14(310D) BAC Dev Obj ID 0 BAC Dev Obj Id 0 BACnet device object ID Default: 1Range: 0 to FFFF 252H5-15(310E) BAC Dev Obj ID 1 BAC Dev Obj Id 1 BACnet device object ID Default: 0Range: 0 to 3F 252<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.A.9 H Parameters: Multi-Function Terminals212 YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual