D.7 Metasys N2 Point DatabaseThis section describes the Metasys N2 point database. This database features 100 logical points: 38 Analog Inputs (AI), 32Analog Outputs (AO), 19 Binary Inputs (BI) and 11 Binary Outputs (BO). These points configure, control, and monitor theoperation of the drive.u Metasys N2 Analog Input (AI) SummaryTable D.4 Metasys N2 Analog Input Summary (Z1000 to Metasys N2)Object ID Object Name Units Z1000 ParameterAI 1 Speed Reference 0.01 Hz U1-01AI 2 Output Speed 0.01 Hz U1-02AI 3 Output Current 0.1 A U1-03AI 4 kWatt Hour Meter kWh U4-10AI 5 Output Power 0.1 kWh U1-08AI 6 Drive Temperature 1 °C U4-08AI 7 PI Feedback 0.01% U5-01AI 8 AC Output Voltage 0.1 Vac U1-06AI 9 DC Bus Voltage 1 Vdc U1-07AI 10 Fault Code – U2-01AI 11 Elapsed Time - Hours 1 hour U4-01AI 12 Elapsed Time - 10K Hours 10K hours U4-01AI 13 MWatt Hour meter MWh U4-11AI 14 Drive Rated Current A n9-01AI 15 Communication Error Code – U1-19AI 16 PI Deviation 0.01% U5-02AI 17 PI Output Capacity 0.01% U5-03AI 18 PI Reference 0.01% U5-04AI 19 Last Fault Code – U2-02AI 20 Freq Ref @ Fault 0.01 Hz U2-03AI 21 Output Freq @ Fault 0.01 Hz U2-04AI 22 Output Current @ Fault 0.1 A U2-05AI 23 Out Volt Ref @ Fault 0.1 Vac U2-07AI 24 DC Bus Volts @ Fault 1 Vdc U2-08AI 25 Output Power @ Fault 0.1 kW U2-09AI 26 Input Term Status @ Fault – U2-11AI 27 Output Term Status @ Fault – U2-12AI 28 Operation Status @ Fault – U2-13AI 29 Elapsed Operation Time @ Fault 1 hour U2-14AI 30 Most Recent Fault – U3-01AI 31 2nd Most Recent Fault – U3-02AI 32 3rd Most Recent Fault – U3-03AI 33 4th Most Recent Fault – U3-04AI 34 Elapsed Time @ Current Fault 1 hour U3-11AI 35 Elapsed Time @ 2nd Fault 1 hour U3-12AI 36 Elapsed Time @ 3rd Fault 1 hour U3-13AI 37 Elapsed Time @ 4th Fault 1 hour U3-14AI 38 Read Parameter Data – –D.7 Metasys N2 Point Database296 YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual