A.8 F: Communication Option Parametersu F6, F7: Communication Option CardParameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/IP, Modbus TCP/IP, and LONWORKSoptions. F7 parameters are used for the EtherNet/IP and Modbus TCP/IP options.No.(Addr.Hex) Name LCD Display Description Values PageF6-01(3A2) Communications ErrorOperation SelectionComm Bus Flt Sel0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only0: Ramp to stop. Decel to stop using the decel time in C1-02.1: Coast to stop.2: Fast Stop. Decel to stop using the decel time in C1-09.3: Alarm only. <1>Default: 1Range: 0 to 3 70F6-02(3A3)External Fault fromComm. OptionDetection SelectionEF0 Detection0: Always Detected1: Only During Run0: Always detected.1: Detection during run only. Default: 0Range: 0, 1 70F6-03(3A4)External Fault fromComm. OptionOperation SelectionEF0 Fault Action0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only0: Ramp to stop. Decel to stop using the decel time in C1-02.1: Coast to stop.2: Fast Stop. Decel to stop using the decel time in C1-09.3: Alarm only. <1>Default: 1Range: 0 to 3 70F6-06(3A7)Torque Reference/Torque Limit Selectionfrom Comm. OptionTorq Ref/Lmt Sel0: Disabled1: EnabledOLV/PMOLV/PM0: Disabled. Torque reference/limit from option board disabled.1: Enabled. Torque reference/limit from option board enabled.Default: 0Range: 0, 1 70F6-07(3A8)Multi-Step SpeedEnable/DisableSelection when NefRef/ComRef is SelectedFref PrioritySel0: Net/Com REF1: MultiStep Speed0: Multi-step reference disabled (same as F7)1: Multi-step reference enabled (same as V7) Default: 0Range: 0, 1 70F6-08(36A)<3>Reset CommunicationParametersCom Prm Init Sel0: Init Com Prms1: No Init Com Prms0: Communication-related parameters (F6-oo) are not resetwhen the drive is initialized using A1-03.1: Reset all communication-related parameters (F6-oo) whenthe drive is initialized using A1-03.Default: 0Range: 0, 1 71F7-01(3E5)<4> <5><6>IP Address 1 IP Address 1 Sets the most significant octet of network static IP address. Default: 192Min.: 0Max.: 255 –F7-02(3E6)<4> <5><6>IP Address 2 IP Address 2 Sets the second most significant octet of network static IPaddress.Default: 168Min.: 0Max.: 255 –F7-03(3E7)<4> <5><6>IP Address 3 IP Address 3 Sets the third most significant octet of network static IP address. Default: 1Min.: 0Max.: 255 –F7-04(3E8)<4> <5><6>IP Address 4 IP Address 4 Sets the fourth most significant octet of network static IPaddress.Default: 20Min.: 0Max.: 255 –F7-05(3E9)<6> Subnet Mask 1 Subnet Mask 1 Sets the most significant octet of network static Subnet Mask. Default: 255Min.: 0Max.: 255 –F7-06(3EA)<6> Subnet Mask 2 Subnet Mask 2 Sets the second most significant octet of network static SubnetMask.Default: 255Min.: 0Max.: 255 –F7-07(3EB)<6> Subnet Mask 3 Subnet Mask 3 Sets the third most significant octet of network static SubnetMask.Default: 255Min.: 0Max.: 255 –F7-08(3EC)<6> Subnet Mask 4 Subnet Mask 4 Sets the fourth most significant octet of network static SubnetMask.Default: 0Min.: 0Max.: 255 –A.8 F: Communication Option ParametersYASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual 201A Parameter List