Gain = 100%Bias = 30%Gain = 100%Bias = 0%Gain 100%Bias 30%Gain 100%Bias 0%Monitor ValueMonitor Value0 V3 V10 V100%0%Output VoltageOutput VoltageH4-07, 08 = 0 H4-07, 08 = 110V-10 V100%3 V-4 V-100%Figure 1.56 Analog Output Gain and Bias Setting Example 3n H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level SelectionSets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parametersH4-07 and H4-08.Set jumper S5 on the terminal board accordingly when changing these parameters.No. Name Setting Range DefaultH4-07 Multi-Function Analog Output Terminal FMSignal Level Selection 0 to 2 0H4-08 Multi-Function Analog Output Terminal AMSignal Level Selection 0 to 2 0Setting 0: 0 to 10 VSetting 1: -10 V to 10 VSetting 2: 4 to 20 mAu H5: Serial Communication (APOGEE FLN, BACnet, MEMOBUS/Modbus,and Metasys N2)Serial communication is possible in the drive using the built-in RS-422/RS-485 port (terminals R+, R-, S+, S-) andprogrammable logic controllers (PLCs) or similar devices running the APOGEE FLN, BACnet, MEMOBUS/Modbus, andMetasys N2 protocols.The H5-oo parameters set the drive for APOGEE FLN, BACnet, MEMOBUS/Modbus, and Metasys N2 communications.Refer to the different communication protocol chapters for detailed descriptions of the H5-oo parameters.1.7 H: Terminal Functions98 YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual