Trap/EventID FALSELCD Message No LCD message display defined.Initial Default. NoneFilterVisibility IPMI Alert SNMPAlert EmailAlert LC Log LCD Power Off PowerCycle ResetFALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSEPWR8584Message Chassis Management Controller is unable to turn on server-arg1because the power supplyredundancy is lost and Performance Over Power Redundancy feature is disabled and thepower required is less than the available power.Arguments •arg1 = slot numberDetailedDescriptionIf power redundancy is lost and the server Performance Over Power Redundancy feature isdisabled, the server turn-on will not be allowed.RecommendedResponse ActionTo enable the server to be turned-on, on the Power Configuration page in the Web UI, enablethe server Performance Over Power Redundancy option . Using the RACADM utility, tun thefollowing command "racadm config -g cfgChassisPower -ocfgChassisPerformanceOverRedundancy 1". Then retry the oepration.Category AuditSubCategory PWR = Power UsageSeverity Severity 3 (Informational)Trap/EventID FALSELCD Message No LCD message display defined.Initial Default. NoneFilterVisibility IPMI Alert SNMPAlert EmailAlert LC Log LCD Power Off PowerCycle ResetFALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSEPWR8585Message Chassis Management Controller granted the power required to turn on server-arg1.Arguments •arg1 = slot numberDetailedDescriptionChassis Management Controller granted the power required to turn on the server identified inthe message.589