USING THE IPMI TOOL SETEATON Managed ePDU User’s Guide 164201xxx Rev 1 DRAFT 10−OCT−2008100thresh Purpose:Sets a particular sensor threshold value. The sensor is specified by name. Validthresholds are: unr Upper Non−Recoverable ucr Upper Critical unc Upper Non−Critical lnc Lower Non−Critical lcr Lower Critical lnr Lower Non−RecoverableExample:$ ipmitool −I lan −H test−pdupcr20−20 −U admin −P pass sensorget “R.14 Current” unr 10.5OEM CommandsYou can use the OEM commands to manage and control the operation of the ePDU.OEM Net−fn is as defined below:#define IPMI_NETFN_OEM_PP0x3CTable 9 lists each OEM command and gives its ID. The sections that follow explaineach command in greater detail.Table 9. OEM Command IDsCommand Name IDSet Power On Delay 0x10Get Power On Delay 0x11Set Socket State 0x12Get Socket State 0x13Set Group State 0x14Set Group Membership 0x15Get Group Membership 0x16Set Group Power On Delay 0x17Get Group Power On Delay 0x18Set Socket ACL 0x19Get Socket ACL 0x1ASet Sensor Calibration 0x1BTest Actors 0x1CTest Sensors 0x1DSet Power Cycle Delay 0x1EGet Power Cycle Delay 0x1F