USING THE WEB INTERFACEEATON Managed ePDU User’s Guide 164201xxx Rev 1 DRAFT 10−OCT−2008 81Configuring the SNMP SettingsThe SNMP Settings page allows you to enable and disable SNMP communicationbetween an SNMP manager and the ePDU. Enabling SNMP communication allowsthe ePDU to send SNMP trap events to the manager, and allow the manager toretrieve and control the power status of each outlet.To configure SNMP communication (necessary for passing SNMP traps and individualoutlet control):1. Select Device Settings, and then select SNMP Settings. The SNMP Settings pagedisplays.Figure 78. SNMP Settings Page2. Select the Enable SNMP Agent check box to enable the ePDU to communicatewith external SNMP managers. A number of options will then become available.3. Select the Enable SNMP v1 / v2c Protocol check box to enable communication withan SNMP manager using SNMP v2c protocol.4. Type the SNMP read−only community string in the Read Community field5. Type the read/write community string in the Write Community field.6. Select the Enable SNMP v3 Protocol check box to enable communication with anSNMP manager using SNMP v3 protocol.7. Type the system location in the System Location field.8. Type the system contact in the System Contact field.9. Click the link at the bottom of the page to download an SNMP MIB for yourePDU to use with your SNMP manager.10. Click Apply. The SNMP configuration is set.