USING THE IPMI TOOL SETEATON Managed ePDU User’s Guide 164201xxx Rev 1 DRAFT 10−OCT−2008104Set Socket ACLRequest Data 1 Socket number2 Number of ACL entries to follow3+NACL entry[7] 0b = deny, 1b = allow[6] 0b = user id, 1b = privilege level[5–0] user id or privilege level depending on [6]Response Data 1 Completion CodeGet Socket ACLRequest Data 1 Socket numberResponse Data 1 Completion Code2 Number of ACL entries to follow3+NACL entry[7] 0b = deny, 1b = allow[6] 0b = user id, 1b = privilege level[5−0] user id or privilege level depending on [6]Set Sensor CalibrationSensor calibration is only allowed for threshold−based sensors that return a sensorreading byte with the Get Sensor Reading command. Also, not all threshold−basedsensors have the capability to be calibrated.Request Data 1 Sensor number (fhh = reserved)2 Actual sensor reading value.Assumes, that at the time this command is executed a calibratedmeasurement is applied to the sensor.Response Data 1 Completion Code00h – If calibration OKCDh – If the sensor cannot be calibratedTest ActorsUsed for hardware testing during production.Request Data 1 [7–2] reserved[1] Beeper test, 0b = disable, 1b = enable[0] 7 segment display test, 0b = disable, 1b = enableResponse Data 1 Completion Code