USING THE WEB INTERFACEEATON Managed ePDU User’s Guide 164201xxx Rev 1 DRAFT 10−OCT−2008 55Setting the ePDU ThresholdsTo set the ePDU thresholds:1. Select Device Settings, and then select Unit Setup. The Unit Setup page displays(see Figure 51).Figure 51. Unit Setup Page2. Type a number in the Delay until outlets are switched on again after outlet reset field.When the outlets on the ePDU are power cycled, they are turned off and thenback on. The number you enter here determines the length of time (in seconds) ittakes for the outlets to turn back on after they are shut down during the powercycle. The default is 10 seconds.NOTE The number you enter here applies to all outlets on the ePDU. However, you can override thisnumber for specific outlets. See Setting Outlet Thresholds" on page 58. You can power cycle an outlet fromthe Outlet Details page. See Power Cycling an Outlet" on page 59 for instructions.3. Type a number of seconds in the Sequence Delay field. The default is200 milliseconds.4. Set the RMS voltage, current, and temperature thresholds for the ePDU in theThresholds panel. For each setting, enter critical and non−critical thresholds.5. Click Apply. The delays and thresholds are applied.