Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06 149Verify washed filters are thoroughly dry before reinstalling.Vérifier que les filtres sont bien secs avant de les réinstaller.a. Remove one top screw and two bottom screws securing each PM section front panel (see Figure 15).Lift the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.b. On the inside of the PM front panels remove the nuts and filter trays holding the filters to the panel.Remove the filters and retain the hardware (see Figure 110).c. Install the washed or new PM section filters with the filter trays and nuts.d. Reinstall the PM section front panels removed in Step a. and secure with the retained hardware.e. Remove one top screw and two bottom screws securing each ISBM section front panel (seeFigure 14). Lift the panel straight up to remove it from the panel hanger bracket at the top of thecabinet.f. If the UPS is a continuous static switch configuration, unfasten the front door latch and swing the dooropen (see Figure 14).g. Pull the foam filters over the screw heads on the cabinet mounted studs and remove the filters fromthe cabinet.h. Push the washed or new foam filters over the screw heads on the cabinet mounted studs until seatedagainst the cabinet.i. Reinstall the PM section front panels removed in Step a. and secure with the retained hardware.j. Reinstall the ISBM section front panel removed in Step b. and secure with the retained hardware.k. If opened, close the front door and secure the latch.UPS Maintenance