58 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06Table 15. TB1, TB2, and TB3 Interface ConnectionsTerminal TB1 Name Description1 REPO NC Input: Normally closed dry contact used to activate UPS EPO from a remoteswitch.2 REPO Return3 REPO NO Input: Normally open dry contact used to activate UPS EPO from a remoteswitch.4 REPO Return5 Battery Aux Input: Normally open contact used to indicate when UPS battery breaker isopen or closed.6 Battery Aux Common7 48 Vdc Battery Shunt Trip + Output: Contacts used to open battery breaker or disconnect.8 48 Vdc Battery Shunt Trip9 Output Contactor K3 NCAuxOutput: Normally closed contact opens when output contactor closes.10 Output Contactor K3 NCAux CommonTerminal TB2 Name Description1 Pull Chain Output: Backup control for parallel operation.2 Pull Chain Common3 Alarm Relay NC Output: General purpose normally-closed (NC) relay contact.4 Alarm Relay Common5 Alarm Relay NO Output: General purpose normally-open (NO) relay contact.6 Alarm Relay Common7 Not Used8 Not Used9 Not Used10 Not UsedTerminal TB3 Name Description1 Building Alarm 1 Input: Programmable UPS alarm, activated by a remote dry contact closure.2 Building Alarm 1 Return3 Building Alarm 2 Input: Programmable UPS alarm, activated by a remote dry contact closure.4 Building Alarm 2 Return5 Building Alarm 3Default: Charger OffInput: Programmable UPS alarm, activated by a remote dry contact closure.Default function set for charger off.6 Building Alarm 3 Return7 Building Alarm 4Default: On GeneratorInput: Programmable UPS alarm, activated by a remote dry contact closure.Default function set for on generator.8 Building Alarm 4 ReturnUPS System Installation