80 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 0655..44 IInnssttaalllliinngg aann OOppttiioonnaall RReellaayy IInntteerrffaaccee MMoodduullee IIIITo install RIM II wiring:1. Verify the UPS system is turned off and all power sources are removed. SeeChapter 7 UPS Operating Instructions for shutdown instructions.2. Perform the procedure listed in paragraph5.1 Installing an Optional Powerware Hot Sync CAN Bridge Card.NOTE If mounting to a hollow wall, secure the enclosure to a wood or metal stud within thewall. Do not use hollow wall anchors.3. Securely mount the RIM II at the desired location. See Figure 51 for mounting hole locations.NOTE When installing signal wiring for CAN card J3 terminals, conduit must be installedbetween the device and the UPS cabinet.4. Remove the UPS cabinet top interface conduit landing plates to drill or punch conduit holes (see Figure 27).5. Reinstall the conduit landing plate.6. Install conduit between the UPS and RIM II. See Figure 51 for RIM II knockout hole location.7. Install wiring between the UPS and RIM II. See Figure 42 and Table 17 for the Powerware Hot Sync CANBridge Card terminal location and wiring information, and Figure 45, Figure 46, and Table 21 for the RIM IIterminal location and wiring information.NOTE 120 Vac for the RIM II should be supplied from the critical bus by facility planners or thecustomer.8. Install 120 Vac power wiring from the critical bus to the RIM II. See Figure 45, Figure 46, and Table 21 forthe terminal location and wiring information.9. Close the front door and secure the latch.10. Restart the UPS. See Chapter 7 UPS Operating Instructions for startup instructions.NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by anauthorized Eaton Customer Service Engineer. Contact an Eaton service representativeto schedule a date.11. Contact an Eaton service representative for verification and testing of the RIM II and its connections priorto making connections with J1 through J4 (see Table 22 and Figure 47).You can order interface cables separately for connecting to the 15–Pin D–Sub Connectors.Table 22. J1 through J4 Interface ConnectorsStatus J1 through J4 DescriptionUPS AVAILABLE Pins 1 and 12 Contacts are closed when the UPS isoperating in Online mode or ready tosupply the load.UPS OFFLINE Pins 3 and 13 Contacts are open when the UPS isoffline. Contacts are closed when theUPS is operating in Online mode.Installing Options and Accessories