Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06 77Table 20. Pull-Chain Wiring Terminations with MOBsFrom To FunctionUPS 1 CAN Bridge Card J3–1 (Alarm) MOB 1 Aux 1 NCMOB Open AlarmUPS 1 CAN Bridge Card J3–2 (AlarmReturn) MOB 1 Aux 1 ComUPS 1 TB2–1 (Pull Chain) MOB 1 Aux 2 NO Pull ChainUPS 2 TB2–2 (Pull Chain Common) UPS 2 TB2–2 (Pull Chain Common) Pull Chain CommonUPS 2 CAN Bridge Card J3–1 (Alarm) MOB 2 Aux 1 NCMOB Open AlarmUPS 2 CAN Bridge Card J3–2 (AlarmReturn)MOB 2 Aux 1 ComUPS 2 TB2–1 (Pull Chain) MOB 2 Aux 2 NO Pull ChainUPS 2 TB2–2 (Pull Chain Common) UPS 3 TB2–2 (Pull Chain Common) Pull Chain CommonUPS 3 CAN Bridge Card J3–1 (Alarm) MOB 3 Aux 1 NCMOB Open AlarmUPS 3 CAN Bridge Card J3–2 (AlarmReturn)MOB 3 Aux 1 ComUPS 3 TB2–1 (Pull Chain) MOB 3 Aux 2 NO Pull ChainUPS 3 TB2–2 (Pull Chain Common) UPS 4 TB2–2 (Pull Chain Common) Pull Chain CommonUPS 4 CAN Bridge Card J3–1 (Alarm) MOB 4 Aux 1 NCMOB Open AlarmUPS 4 CAN Bridge Card J3–2 (AlarmReturn)MOB 4 Aux 1 ComUPS 4 TB2–1 (Pull Chain) MOB 4 Aux 2 NO Pull ChainMOB 1 Aux 2 Com MOB 2 Aux 2 ComPull Chain MOB CommonMOB 2 Aux 2 Com MOB 3 Aux 2 ComMOB 3 Aux 2 Com MOB 4 Aux 2 Com55..33 IInnssttaalllliinngg aann OOppttiioonnaall RReemmoottee MMoonniittoorr PPaanneell IIIITo install RMP II wiring:1. Verify the UPS system is turned off and all power sources are removed. SeeChapter 7 UPS Operating Instructions for shutdown instructions.2. Perform the procedure listed in paragraph5.1 Installing an Optional Powerware Hot Sync CAN Bridge Card.NOTE If mounting to a hollow wall, secure the enclosure to a wood or metal stud within thewall. Do not use hollow wall anchors.Installing Options and Accessories