Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06 25Table 10. Recommended Installation Parts and Tools (Not Supplied by Eaton) (Continued)Part Size Quantity Manufacturer Part Number Notes350 MCM Thomas & Betts 54872BE400 MCM Thomas & Betts 54874BE500 MCM Thomas & Betts 54876BEManual Hydraulic Crimp Tool 14 Ton 1 Thomas & Betts TBM14MDie Set N/A 1 Thomas & Betts 15506Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 11 for conduitrequirements.Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit. Neutral and groundmust be run in the same conduit as the phase conductors.Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one groundconductor sized in accordance with NEC Table 250.122.Conduit sizes listed are for copper wiring only.Table 11. 480V Power Cable Conduit RecommendationsUPS Model Voltage TerminalNumber ofWires inConduitMinimumConduitTrade SizeNumberofConduitsEaton 9395C-1000/1000Eaton 9395C-1000/1100480 VacAC Input to UPS Rectifier(A, B, C, Ground) 4 3 5AC Input to Bypass andOutput(A, B, C, Ground)4 3 5DC (CommonBattery)Battery(Positive, Negative, Ground) 5 3.5 5Eaton 9395C-1100/1100480 VacAC Input to UPS Rectifier(A, B, C, Ground) 4 3 6AC Input to Bypass andOutput(A, B, C, Ground)4 3 5DC (CommonBattery)Battery(Positive, Negative, Ground) 7 4 4Battery Conductor Routing: Refer to the notes at the bottom of Table 5 Input/Output Ratings and ExternalWiring Requirements.External overcurrent protection and disconnect are not provided by this product, but are required by codes.Refer to Table 5 for wiring requirements. If an output lockable disconnect is required, it is to be supplied by thecustomer.Table 12 lists the recommended rating for input circuit breakers with breaker ratings for rectifier input.UPS Installation Plan and Unpacking