42 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 0611. Connect the ground braid to the PM section ground bolt and secure.NOTE Intercabinet interface wiring harnesses are supplied coiled inside the protective cage onthe right side panel of the ISBM section (see Figure 21).12. In the ISBM section (see Figure 21), locate the coiled wiring harnesses with the J50, J51, J56, J61, J70and P60 connectors attached. Remove the wire ties securing the harnesses and carefully remove theharnesses from the protective cage. If necessary, loosen the screws securing the protective cage.13. Locate the mating P50 connector in the PM section wireway (see Figure 21) and connect the P50connector to the J50 connector.14. Locate the mating P51 connector in the PM section wireway (see Figure 21) and connect the P51connector to the J51 connector.15. Locate the mating P56 connector in the PM section wireway (see Figure 21) and connect the J56connector to the J56 connector.16. Locate the mating J60 connector in the PM section wireway (see Figure 21) and connect the J60connector to the P60 connector.17. Locate the mating P61 connector in the PM section wireway (see Figure 21) and connect the P61connector to the J61 connector.18. In the PM section (see Figure 21), locate the coiled RJ-45 CAN cable. Remove the wire ties securing thecable to the interior left side panel of the PM section. Route this cable through the round wiring access inthe right side panel of the ISBM section (see Figure 21).19. In the ISBM section, locate the J39 inverter CAN connector on the Pl1 interface board and connect the RJ-45 CAN cable connector to the J39 connector (see Figure 21 and Figure 22).20. Dress the interface harnesses and secure in place with wire ties as necessary to prevent wire damage.21. When all wiring is complete, reinstall the safety shield panels removed in previous steps.22. Reinstall the front wireway panel.UPS System Installation