Operation Manual – PoEH3C S9500 Series Routing Switches Chapter 2 PoE PSU Supervision Configuration2-2Note:z You can set the thresholds to any appropriate values in the range, but make surethe lower threshold is less than the upper threshold.z For 220 VAC input, it is recommended to set the upper threshold to 264 V and thelower threshold to 181 V.z For 110 VAC input, it is recommended to set the upper threshold to 132 V and thelower threshold to 90 V.2.2.2 AC Input Alarm Thresholds Configuration ExampleI. Network requirementsz Set the overvoltage alarm threshold of AC input for PoE PSUs to 264.0 V.z Set the undervoltage alarm threshold of AC input for PoE PSUs to 181.0 V.II. Configuration procedure# Enter system view. system-view# Set the overvoltage alarm threshold of AC input for PoE PSUs to 264.0 V.[H3C] poe-power input-thresh upper 264.0# Set the undervoltage alarm threshold of AC input for PoE PSUs to 181.0 V.[H3C] poe-power input-thresh lower 181.0# Display the information about the AC input for the PoE PSUs.[H3C] display poe-power ac-input state2.3 DC Output Alarm Thresholds ConfigurationYou can set the DC output alarm thresholds for the PoE PSUs to enable the S9500series to monitor the DC output voltages of the PSUs in real time through the PoEsupervision module.2.3.1 DC Output Alarm Thresholds Configuration TasksTable 2-2 DC output alarm thresholds configuration tasksNo Operation Command Description1 Enter system view system-view -2Set the overvoltage alarmthreshold of DC output (upperthreshold) for the PoE PSUspoe-poweroutput-thresh upperstringRequired, and therange is 55.0 V to57.0 V.