Setting Examples C through EExample = C 90 Hz Example = D 120 Hz Example = E 180 Hz012162001.5 3 9060Voltage (V)Frequency (Hz)012162001.5 3 12060Voltage (V)Frequency (Hz)012162001.5 3 18060Voltage (V)Frequency (Hz)u Motor Parameters: E2-01 to E2-03n Setting Motor ParametersThe following table provides instructions on how to set motor parameters. Refer to the motordata sheet for the correct motor data.No. Parameter Name Setting MethodE2-01 Motor Rated Current Sets the motor nameplate full load current in amperes (A).E2-02 Motor Rated SlipCalculate and set the motor rated slip based on the rated speed described on themotor nameplate.Motor rated slip = Motor rated frequency [Hz] - Rated speed [r/min] x No. ofmotor poles / 120.E2-03 Motor No-Load CurrentSet motor no-load current at rated voltage and rated frequency.Contact the motor manufacturer to get the no-load current. This information isnot usually written on the motor nameplate.The default no-load current is for a Yaskawa 4-pole motor.E2-05 Motor Line-to-LineResistance Sets the phase-to-phase motor resistance in ohms.u Digital Output: H2-01Parameter H2-01 assigns functions to digital output terminals MA, MB, and MC. Set thisparameter as required by the application. Default value is listed below.NOTICE: Do not assign a function that repeats ON/OFF frequently to terminals MA and MB. Failure to complywill reduce the relay contact lifetime. The expected number of relay contact switching times is normally200,000 times (current 1 A, resistance load).No. Parameter Name DefaultH2-01 Terminal MA, MB and MC Function Selection (relay) E: FaultNote: The setting range for H2-01 is 0 to 13D. Refer to Parameter List on page 197 for more information.4.5 Basic OperationYASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual 1034 Start-Up Programming& Operation