B.2 Parameter Tableu A: Initialization ParametersThe A parameter group creates the operating environment for the drive. This includes theparameter Access Level, and Password.No. Name Description Range Def. Mode Addr.Hex Pg.V/fA1: Initialization ParametersUse A1 parameters to configure the basic environment for drive operation.A1-01<22> Access LevelSelectionSelects which parameters are accessible via the digitaloperator.0: Operation only2: Advanced Access Level0, 2 2 O 101 116A1-03 InitializeParametersResets all parameters to factory default settings.(Initializes the drive then returns A1-03 to 0)0: No Initialize2220: 2-Wire Initialization3330: 3-Wire Initialization0 to3330 0 O 103 87U2 monitors are not reset whenperforming initialization.A1-04 Password 1When the value set into A1-04 does not match thevalue set into A1-05, parameters A1-01 and A1-03cannot be changed.0 to9999 0 O 104 116A1-05 Password 20 to9999 0 O 105 116This parameter is hidden from view. Toaccess A1-05, first display A1-04. Thenpress the STOP key while holding downthe up arrow key. Parameter A1-05 willappear.<22> Parameter can be changed during run.u b: ApplicationApplication parameters configure the Run Command Source, DC Injection Braking, and otherapplication-related settings.No. Name Description Range Def. Mode Addr.Hex Pg.V/fb1: Operation Mode SelectionUse b1 parameters to configure the operation mode.b1-01 FrequencyReferenceSelectionSelects the frequency reference input source.0: Operator - Digital preset speed d1-01 to d1-171: Terminals - Analog input terminal2: MEMOBUS/Modbus communications (option)3: Potentiometer (option)0 to 3 1 S 180 87b1-02 Run CommandSelectionSelects the run command input source.0: Operator - RUN and STOP keys on the digitaloperator1: Digital input terminals2: MEMOBUS/Modbus communications (option)0 to 2 1 S 181 89B.2 Parameter TableYASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual 199B Parameter List