u H Parameters: Multi-Function TerminalsH parameters assign functions to the multi-function input and output terminals.No. Name Description Range Def. Mode Addr.Hex Pg.V/fH1: Multi-Function Digital InputH1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F".H1-01 Multi-Function DigitalInput Terminal S1Function SelectionAssigns a function to the multi-functiondigital inputs.Refer to H1 Multi-Function Digital InputSelections on page 206 for a description ofsetting values.1 to 6740 O 438 —H1-02 Multi-Function DigitalInput Terminal S2Function Selection 41 O 439 —H1-03 Multi-Function DigitalInput Terminal S3Function Selection0 to 6724 O 400 —H1-04 Multi-Function DigitalInput Terminal S4Function Selection 14 O 401 —H1-05 Multi-Function DigitalInput Terminal S5Function Selection3 (0)<18> O 402 —<18> Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization.H1 Multi-Function Digital Input SelectionsH1-ooSetting Function Description ModeV/f0 3-Wire Sequence Closed: Reverse rotation (only if the drive is set up for 3-Wiresequence) O1 LOCAL/REMOTE Selection Open: REMOTE, Reference 1 (b1-01/02)Closed: LOCAL, LED operator is run and reference source O2 External Reference 1/2 Open: Run and frequency reference source 1 (b1-01/02)Closed: MEMOBUS/Modbus Communication O3 Multi-Step Speed Reference 1Used to select Multi-Step Speeds set in d1-01 to d1-08O4 Multi-Step Speed Reference 2 O5 Multi-Step Speed Reference 3 O6 Jog Reference Selection Open: Selected speed referenceClosed: Jog Frequency reference (d1-17). Jog has priority overall other reference sources. O7 Accel/Decel Time 1 Used to switch between Accel/Decel Time O8 Baseblock Command (N.O.) Open: Normal operationClosed: No drive output O9 Baseblock Command (N.C.) Open: No drive outputClosed: Normal operation OA Accel/Decel Ramp Hold Closed: The drive pauses during acceleration or deceleration andmaintains the output frequency. OF Not used Select this setting when not using the terminal or when using theterminal in a pass-through mode. OB.2 Parameter Table206 YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual