No. Name Description Range Def. Mode Addr.Hex Pg.V/fd3-04 JumpFrequencyWidthThis parameter sets the dead-band width around eachselected prohibited frequency reference point. Thebandwidth becomes the designated Jump frequency,plus or minus d3-04.0.0 to20.0 1.0Hz O 297 —d4: Frequency Reference HoldUse d4 parameters to configure the drive frequency reference hold function.d4-01FrequencyReferenceHold FunctionSelectionDetermines if the frequency reference or frequencyreference bias is saved when the Run command isremoved or the power goes off.0: Disabled1: EnabledThis parameter is effective when the multi-functioninputs “Accel/Decel Ramp Hold”, “Up/Down” or“Up/Down 2” commands are selected (H1-oo = Aor 10/11).0, 1 0 O 298 —<19> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, FrequencyReference Upper Limit.<22> Parameter can be changed during run.u E: Motor ParametersE parameters set V/f characteristics and motor-related data.No. Name Description Range Def. Mode Addr.Hex Pg.V/fE1: V/f Pattern CharacteristicsUse E1 parameters to set V/f characteristics for the motor.E1-01<24>Input VoltageSettingThis parameter must be set to the power supplyvoltage.WARNING! Drive input voltage (not motor voltage)must be set in E1-01 for the protective features of thedrive to function properly. failure to do so may resultin equipment damage and/or death or personal injury.155 to255 <14> S 300 99E1-03 V/f PatternSelection F: Custom V/f. E1-04 through E1-10 settings definethe V/f pattern. F F O 302 —B.2 Parameter Table204 YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual