Multi-Function Contact Outputs250 Vac, 10 mA - 1 A30 Vdc, 10 mA - 1 A(standard default setting)MAMBMCFaultFaultFigure 4.17 Digital Output Connection Diagramu Analog Outputs: H4-01 to H4-03Group U parameters can be used to observe the drive status (operating conditions) throughthe LED operator. Analog outputs corresponding to these monitors can be obtained on analogoutput terminal AM when programmed with parameter group H4. Some Group U monitorsare not available as analog outputs.No. Parameter Name DescriptionH4-01 Terminal AM MonitorSelectionSelect the data to output through multi-function analog output terminal AM.Set the desired monitor parameter to the digits available in Uo-oo. Forexample, enter “103” for U1-03.When using this terminal as a through terminal or when not using it at all, set“000” or “031”.H4-02 <1> Terminal AM Output Gain Sets the voltage level gain of terminal AM. The bias to be added ranges from0 to +/- 10% when 10 V is assumed to be 100%.H4-03 <1> Terminal AM Bias Setting Sets the voltage level bias for terminal AM.The bias added is 0 to ±10% with a maximum voltage output of 10 V as 100%.<1> The parameter can be changed during run.n Changing Analog Output SettingsThe following example illustrates how to program analog output terminal AM to generate asignal proportional to drive output current (monitor U1-03).Using H4-01 to Display Monitor ContentsStep Display/Result1. Turn on the power to the drive. The initial display appears.2. Press until the Parameter setting menu is displayed.3. Press to enter the Parameter setting menu.4.5 Basic Operation104 YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual