Step Display/Result6. Press to run the motor at 5 Hz. The RUN light will turn on.STOPOff On7. With SW1 closed, the drive runs the motor at Multi-Step Speed 2(20 Hz).8. With SW1 open and SW2 closed, the drive runs the motor at Multi-Step3 (50 Hz).9. With both SW1 and SW2 closed, the drive runs the motor at Multi-Step4 (60 Hz).10. Press STOP to stop the drive. The RUN light will flash until themotor comes to a complete stop.STOPFlashing Off<1> When the frequency reference is assigned to the LED operator (b1-01=0), the first step in a multi-step speedsequence comes from d1-01.Note: When a run command is input from the control circuit terminal, the frequency reference value is selectedas follows:When b1-01 = 0 and the run command is given, the drive uses the frequency set to d1-01.When b1-01 = 1 and the run command is given, the drive uses the frequency reference value input to analogcontrol terminal A1.u Drive Input Voltage Setting: E1-01Set E1-01 according to the power supply voltage. This setting serves as a base value for certaindrive protective functions.NOTICE: Set drive input voltage (not motor voltage) in parameter E1-01 for proper function of the protectivefeatures of the drive. Failure to comply could result in improper drive operation. Set parameter E1-01 to matchthe input voltage of the drive.Parameter Name Description Setting Range DefaultE1-01 InputVoltageSettingSet to the nominal voltage of the incoming line. Setsthe maximum and base voltage, and adjusts the levelsof drive protective features (e.g., overvoltage, brakingresistor level, stall prevention, etc.).200 V Class: 155 to 255400 V Class: 310 to 510 200 V4.5 Basic OperationYASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual 994 Start-Up Programming& Operation