Single-Phase 200 V Three-Phase 200 V Three-Phase 400 VModel(Capacity)CarrierFrequency(kHz)OutputCurrent(A)Model(Capacity)CarrierFrequency(kHz)OutputCurrent(A)Model(Capacity)CarrierFrequency(kHz)OutputCurrent(A)BA00030.75 kW/0.4 kW2 3.3 2A00040.75 kW/0.4 kW2 3.3 4A00020.75 kW/0.4 kW2 2.110 3.0 10 3.0 8 1.815 2.4 15 2.4 15 1.1BA00061.1 kW/0.75 kW2 6.0— — — 4A00041.5 kW/0.75 kW2 4.110 5.0 8 3.415 4.0 15 2.0— — — 2A00061.1 kW/0.75W2 6.0— — —10 5.015 4.0— — — 2A00081.5 kW/1.1 kW2 8.0— — —8 6.915 5.5BA00102.2 kW/1.5W2 9.6 2A00102.2 kW/1.5W2 9.6 4A00052.2 kW/1.5W2 5.48 8.0 8 8.0 8 4.815 6.4 15 6.4 15 2.9— — — 2A00123.0 kW/2.2 kW2 12.0 4A00073.0 kW/2.2 kW2 6.98 11.0 8 5.515 8.8 15 3.3— — — 2A00183.7 kW/3.0W2 17.5 4A00093.7 kW/3.0 kW2 8.88 14.0 8 7.215 11.2 15 4.3— — — 2A00205.5 kW/4.0 kW2 19.6 4A00115.5 kW/4.0 kW2 11.18 17.5 8 9.215 14.0 15 5.5u Multi-Step Speed Operation (4-Step Speed)Select up to 9 preset references (including Jog reference) using two multi-function inputs S4and S5. Two multi-step references can be selected using two multi-function inputs asillustrated in Figure 4.14.n Multi-Step Speed Operation ParametersNo. Name Descriptiond1-01 Frequency Reference 1 Frequency reference. o1-03 determines the units, with Hz as the default.d1-02 Frequency Reference 2 Frequency reference when multi-function input “Multi-Step Speed Reference1" (H1-oo = 3) is on. Setting unit: set by o1-03.d1-03 Frequency Reference 3 Frequency reference when multi-function input “Multi-Step Speed Reference2” (H1-oo = 4) is on. Setting unit: set by o1-03.4.5 Basic Operation96 YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual