4.3 The Drive and Programming ModesThe drive functions are divided into two main groups accessible via the Digital LED Operator:Drive Mode: The Drive mode allows motor operation and parameter monitoring. Parametersettings cannot be changed when accessing functions in the Drive Mode (Table 4.3).Programming Mode: The Programming Mode allows access to setup/adjust, verifyparameters. The drive prohibits changes in motor operation such as start/stop when the DigitalLED Operator is accessing a function in the Programming Mode.Table 4.3 illustrates the different functions visible as the “Up arrow” is scrolled immediatelyafter powering up the drive.Note: When b1-08 (Run Command Selection while in Programming Mode) is set to 1 (enabled), the drive can runeven if the mode is switched to the programming mode. When setting b1-08 to 0 (disabled), the mode cannotbe switched to the programming mode while the drive is running.Table 4.3 Summary of ModesMode Group Description Key Press LED Digital Operator DisplayDrive Mode Functions(Motor operation andmonitoring)Frequency Reference Display(Initial power-up state)STOPForward/ReverseSTOPOutput Frequency DisplaySTOPOutput Current DisplaySTOPOutput Voltage ReferenceSTOPMonitor DisplaySTOPProgramming Mode Functions(Changing parameters)Verify FunctionSTOPSetup Group ParametersSTOPAll ParametersSTOPu Navigating the Drive and Programming ModesThe drive is set to operate in Drive Mode when it is first powered up. Switch between displayscreens by using the and keys.4.3 The Drive and Programming Modes78 YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual