u Installing Fuses on the Input SideInstall recommended UL-approved fuses at the main power input of the drive. Select fusesaccording to Table 7.3.Table 7.3 Recommended Input Fuse SelectionDrive ModelCIMR-JoClass T Fuses Class L FusesModel Fuse Ampere Rating Model Fuse Ampere Rating200 V Class Single-Phase DrivesBA0001 A6T15 15 CR6L-20/UL 20BA0002 A6T20 20 CR6L-30/UL 30BA0003 A6T20 20 CR6L-50/UL 50BA0006 A6T40 40 CR6L-75/UL 75BA0010 A6T40 40 CR6L-100/UL 100200 V Class Three-Phase Drives2A0001 A6T10 10 CR6L-20/UL 202A0002 A6T10 10 CR6L-20/UL 202A0004 A6T15 15 CR6L-20/UL 202A0006 A6T20 20 CR6L-30/UL 302A0008 A6T25 25 CR6L-50/UL 502A0010 A6T25 25 CR6L-50/UL 502A0012 A6T30 30 CR6L-50/UL 502A0018 A6T40 40 CR6L-75/UL 752A0020 A6T40 40 CR6L-75/UL 75400 V Class Three-Phase Drives4A0001 A6T10 10 CR6L-20/UL 204A0002 A6T10 10 CR6L-20/UL 204A0004 A6T20 20 CR6L-50/UL 504A0005 A6T25 25 CR6L-50/UL 504A0007 A6T25 25 CR6L-50/UL 504A0009 A6T25 25 CR6L-50/UL 504A0011 A6T30 30 CR6L-50/UL 50u Installing a Motor Thermal Overload (oL) Relay on the DriveOutputMotor thermal overload relays protect the motor by disconnecting power lines to the motordue to a motor overload condition.Install a motor thermal overload relay between the drive and motor:• When operating multiple motors on a single AC drive.• When using a power line bypass to operate the motor directly from the power line.7.4 Installing Peripheral Devices178 YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual