u Control Circuit Terminal Block FunctionsDrive parameters determine which functions apply to the multi-function digital inputs (S1 toS5), and multi-function digital outputs (MA, MB). The default is called out next to eachterminal in Figure 3.10.WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after beingwired. Operating a drive with untested control circuits could result in death or serious injury.WARNING! Confirm the drive I/O signals and external sequence before starting test run. Failure to complymay result in death or serious injury.NOTICE: Do not switch an input contactor more often than once every 30 minutes. Improper equipmentsequencing could shorten useful life of the drive electrolytic capacitors and circuit relays. Normally the driveI/O should be used to stop and start the motor.n Input TerminalsTable 3.6 Control Circuit Input TerminalsType No. Terminal Name (Function) Function (Signal Level) Default SettingMulti-FunctionDigitalInputsS1 Multi-function input 1 (Closed: Forwardrun, Open: Stop)24 Vdc, 8 mANote: Drive preset to sinking mode. When usingsource mode, set DIP switch S3 to allow for a 24 Vdc(±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 60.S2 Multi-function input 2 (Closed: Reverse run,Open: Stop)S3 Multi-function input 3 (External fault (N.O.)S4 Multi-function input 4 (Fault reset)S5 Multi-function input 5 (Multi-step speedreference 1)SC Multi-function input common (Controlcommon) Sequence commonMainFrequencyReferenceInputA1 Frequency referenceInput voltage or input current (Selected by DIP switchS1 and H3-01) 0 to +10 Vdc (20 kΩ),Resolution: 1/10004 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω),Resolution: 1/500+V Analog input power supply +10.5 Vdc (max allowable current 20 mA)AC Frequency reference common 0 Vdcn Output TerminalsTable 3.7 Control Circuit Output TerminalsType No. Terminal Name (Function) Function (Signal Level) Default SettingMulti-FunctionDigital OutputMA N.O. (fault) Digital output30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 AMinimum load: 5 Vdc, 10 mA (reference value)MB N.C. output (fault)MC Digital output commonMonitor Output AM Analog monitor output 0 to 10 Vdc (2 mA or less) Resolution: 1/256AC Monitor common 0 V3.7 Control Circuit WiringYASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual 553 Electrical Installation