Step Display/Result5. Press the key to access the setting value. (number farthest tothe left flashes)u Switching Between LOCAL and REMOTEEntering the run command using the LED operator is referred to as LOCAL, while enteringthe run command from an external device via the control circuit terminals or network optionunit is referred to as REMOTE.WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is alreadyapplied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or seriousinjury. Be sure all personnel are clear of rotating machinery and electrical connections prior to switchingbetween LOCAL mode and REMOTE mode.There are two ways to switch between LOCAL and REMOTE.Note: 1. After selecting LOCAL, the LO/RE light will remain lit.2. The drive will not allow the user to switch between LOCAL and REMOTE during run.n Using the LO/RE Key on the LED OperatorStep Display/Result1. Turn on the power to the drive. The initial display appears.2. Press . The LO/RE light will light up. The drive is now inLocal.To set the drive for REMOTE operation, press the key again.STOPn Using Input Terminals S1 through S5 to Switch between LO/RESwitch between LOCAL and REMOTE using one of the digital input terminals S1 throughS5 (set the corresponding parameter H1-01 through H1-05 to “1”).Follow the example below to set the digital input terminals.Note: 1. For a list of digital input selections, Refer to Parameter List on page 197.2. Setting a multi-function input terminal to a value of 1 disables the LO/RE key on the LED operator.4.3 The Drive and Programming Modes84 YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual