Drive ModelCIMR-JoClass T FusesClass RK5 FusesModel Fuse AmpereRatingBA0010 A6T40 40 Contact Yaskawa200 V Class Three-Phase Drives2A0001 A6T10 10 Contact Yaskawa2A0002 A6T10 10 Contact Yaskawa2A0004 A6T15 15 Contact Yaskawa2A0006 A6T20 20 Contact Yaskawa2A0008 A6T25 25 Contact Yaskawa2A0010 A6T25 25 Contact Yaskawa2A0012 A6T30 30 Contact Yaskawa2A0018 A6T40 40 Contact Yaskawa2A0020 A6T40 40 Contact Yaskawa400 V Class Three-Phase Drives4A0001 A6T10 10 Contact Yaskawa4A0002 A6T10 10 Contact Yaskawa4A0004 A6T20 20 Contact Yaskawa4A0005 A6T25 25 Contact Yaskawa4A0007 A6T25 25 Contact Yaskawa4A0009 A6T25 25 Contact Yaskawa4A0011 A6T30 30 Contact Yaskawan GroundingThe drive is designed to be used in T-N (grounded neutral point) networks. If installing thedrive in other types of grounded systems, contact your dealer or Yaskawa for instructions.u EMC Guidelines ComplianceThis drive is tested according to IEC61800-3:2004 and it complies with the EMC guidelines.n EMC Filter InstallationThe following conditions must be met to ensure continued compliance with guidelines. Referto EMC Filters on page 233 for EMC filter selection.Installation MethodVerify the following installation conditions to ensure that other devices and machinery usedin combination with this drive also comply with EMC guidelines.1. Install an EMC noise filter to the input side specified byYaskawa for compliance withEuropean standards.2. Place the drive and EMC noise filter in the same enclosure.C.2 European Standards230 YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual