A.2 Single/Three-Phase 200 V Class DriveTable A.2 Power RatingsItem SpecificationThree-Phase: CIMR-Jo2A 0001 0002 0004 0006 0008 0010 0012 0018 0020Single-Phase: CIMR-JoBA <1> 0001 0002 0003 0006 - 0010 - - -Maximum Motor Size Allowed(kW) <2>ND Rating 0.2 0.4 0.75 1.1 1.5 2.2 3.0 3.7 5.5HD Rating 0.1 0.2 0.4 0.75 1.1 1.5 2.2 3.0 3.7InputInputCurrent (A)<3>Three-PhaseND Rating 1.1 1.9 3.9 7.3 8.8 10.8 13.9 18.5 24.0HD Rating 0.7 1.5 2.9 5.8 7.0 7.5 11.0 15.6 18.9Single-PhaseND Rating 2.0 3.6 7.3 13.8 – 20.2 - – –HD Rating 1.4 2.8 5.5 11.0 – 14.1 - – -OutputRated Output Capacity(kVA) <4>ND Rating 0.5 0.7 1.3 2.3 3.0 3.7 4.6 6.7 7.5HD Rating 0.3 0.6 1.1 1.9 2.6 3.0 4.2 5.3 6.7Output Current (A)ND Rating<5> 1.2 1.9 3.5(3.3) 6.0 8.0 9.6 12.0 17.5 19.6HD Rating 0.8 <6> 1.6<6>3.0<6> 5.0 <6> 6.9<7>8.0<7>11.0<7>14.0<7>17.5<7>Overload ToleranceND Rating: 120% of rated output current for 1 minuteHD Rating: 150% of rated output current for 1 minute(Derating may be required for applications that start and stopfrequently)Carrier Frequency 2 kHz (user-set, 2 to 15 kHz)Max Output Voltage (V) Three-phase 200 to 240 V (proportional to input voltage)Max Output Frequency (Hz) 400 Hz (user-adjustable)PowerSupplyRated VoltageRated Frequency Three-phase power: Three-phase 200 to 240 V 50/60 HzSingle-phase power: 200 to 240 V 50/60 HzAllowable Voltage Fluctuation -15 to 10%Allowable Frequency Fluctuation ±5%Harmonic CorrectiveActions DC Reactor Optional<1> Drives with a single-phase power supply input output three-phase power, and cannot run a single-phase motor.<2> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output ampsshould be equal to or greater than the motor rated current.<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, andpower supply impedance.<4> Rated motor capacity is calculated with a rated output voltage of 220 V.<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.<6> Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency.<7> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include ratedinput and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to “0”for HD or “1” for ND (default).A.2 Single/Three-Phase 200 V Class DriveYASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual 189A Specifications