4.18 CMD - auto commandsA Command file at a memory card is automatically executed under the following condi-tions:n CPU is in STOP and memory card is pluggedn After each PowerONn The Command file is a text file, which consists of a command sequence to be storedas vipa_cmd.mmc in the root directory of the memory card.n The file has to be started by CMD_START as 1. command, followed by the desiredcommands (no other text) and must be finished by CMD_END as last command.n Text after the last command CMD_END e.g. comments is permissible, because this isignored.n As soon as the command file is recognized and executed each action is stored at thememory card in the log file logfile.txt.n For each executed command a diagnostics entry may be found in the diagnosticsbuffer.Please regard the command sequence is to be started with CMD_START and ended withCMD_END.Command Description DiagnosticsentryCMD_START In the first line CMD_START is to be located. 0xE801There is a diagnostics entry if CMD_START is missing. 0xE8FEWAIT1SECOND Waits about 1 second. 0xE803LOAD_PROJECT The function "Overall reset and reload from memory card"is executed. The wld file located after the command isloaded else "s7prog.wld" is loaded.0xE805SAVE_PROJECT The recent project (blocks and hardware configuration) isstored as "s7prog.wld" at the memory card. If the file justexists it is renamed to "s7prog.old". If your CPU is pass-word protected so you have to add this as parameter. Oth-erwise there is no project written.Example: SAVE_PROJECT password0xE806FACTORY_RESET Executes "factory reset". 0xE807DIAGBUF The current diagnostics buffer of the CPU is stored as "dia-gbuff.txt" at the memory card.0xE80BSET_NETWORK IP parameters for Ethernet PG/OP channel may be set bymeans of this command. The IP parameters are to begiven in the order IP address, subnet mask and gateway inthe format x.x.x.x each separated by a comma. Enter theIP address if there is no gateway used.0xE80ECMD_END In the last line CMD_END is to be located. 0xE802WEBPAGE Saves all information on the device web page (Expert-View) as webpage.txt on the memory cardÄ Chap. 4.11‘Accessing the web server’ page 930xE804WEBVISU_PGOP_ENABLE Enable WebVisu project via Ethernet PG/OP channel 0xE82CWEBVISU_PGOP_DISABLE* Disable WebVisu project via Ethernet PG/OP channel 0xE82DOverviewCommand fileCommandsVIPA System SLIODeployment CPU 013-CCF0R00CMD - auto commandsHB300 | CPU | 013-CCF0R00 | en | 19-30114