Parameter overviewOperating parameters Description AssignmentOutput format Here specify the range of values for the output. The CPUhereby determines the pulse duration:n Per mil– Output value is within 0 ... 1000– Pulse duration = (Output value / 1000) x perioddurationn S7 Analog value:– Output value is Siemens S7 analog value 0 ...27648– Pulse duration = (Output value / 27648) x perioddurationPer milTime base Here you can set the time base, which will apply for resolu-tion and range of values of the period duration, minimumpulse duration and on-delay.n 1ms: The time base is 1msn 0.1ms: Time base is 0.1ms0.1msOn-delay This parameter is ignored. 0Period duration With period duration you define the length of the outputsequence, which consists of pulse duration and pulsepause.Range of values:Time base 1ms: 1 ... 87msTime base 0.1ms: 0.4 ... 87.0ms50*Minimum pulse duration With the minimum pulse duration you can suppress shortoutput pulses and short pulse pauses. All pulses orpauses, which are smaller than the minimum pulse dura-tion, are suppressed. This allows you to filter very shortpulses (spikes), which can not be recognized by theperiphery.Range of values:Time base 1ms: 0 ... Period duration / 2 · 1msTime base 0.1ms: 2 ... Period duration / 2 · 0.1ms2*) This value can vary depending on the configuration tool and can be out of range. Values, which are out of range are invalid and must be adjusted accordingly!5.9.5 Status indicationDigital output LEDgreenDescriptionDO +0.0 Pulse train 0 has "1" signalPulse train 0 has "0" signalDO +0.1 Pulse train 1 has "1" signalPulse train 1 has "0" signalVIPA System SLIODeployment I/O peripheryPulse train > Status indicationHB300 | CPU | 013-CCF0R00 | en | 19-30160