7.3 Activate OPC UA functionalityFor your CPU can process a OPC UA project, you have to activate the OPC UA function-ality.1. Insert a memory card from VIPA (VSD, VSC) into your CPU. Please note that youmust always use a VSC card suitable for your CPU.Ä Chap. 4.16 ‘Deploymentstorage media - VSD, VSC’ page 1112. Turn on the CPU, to activate the OPC UA functionality, you have to establish anOverall reset.ð As long as the memory card is inserted, the OPC UA functionality remains acti-vated even after a power cycle. When the project is transferred from the OPCUA Configurator, the OPC UA project is automatically transferred to the insertedmemory card.Please regard that the memory card must remain plugged whenyou’ve executed activated the OPC UA functionality. Otherwisethe SF LED is on and the OPC UA functionality is deactivatedafter 72 hours. As long as an activated memory card is notinserted, the SF LED is on and the "TrialTime" timer countsfrom 72 hours down to 0. After that the OPC UA functionality isde-activated. By inserting the memory card, the LED goes offand the CPU runs again without restrictions.Please note that the use of a OPC UA project, depending onthe scope of the OPC UA project and the PLC project, can influ-ence the performance and thus the response time of your appli-cation.7.4 Usage in VIPA SPEED7 Studion VIPA SPEED7 Studio from Version V1.8.6– The functionality for the OPC UA configuration is integrated in the SPEED7Studio. For more information, see the according online help.7.5 Usage in Siemens SIMATIC ManagerSiemens SIMATIC Manager from V5.5 and VIPA SPEED7 Studio from V1.8.6n The OPC UA configuration happens by the external OPC UA Configurator from VIPA.n The OPC UA Configurator is the SPEED7 Studio reduced to OPC UA functionality.n The OPC UA Configurator can be registered in the Siemens SIMATIC Manager bymeans of the SPEED7 Tools Integration.n The OPC UA Configurator is to be called from the Siemens SIMATIC Manager afterproject creation and online configuration.n The OPC UA Configurator automatically imports the data for the OPC UA configura-tion from the project data of the Siemens SIMATIC Manager.n The OPC UA configuration is transferred online from the OPC UA Configurator. TheOPC UA Configurator automatically imports the data for the OPC UA configurationfrom the project data of the Siemens SIMATIC Manager.ProceedingPreconditionPreconditionVIPA System SLIODeployment OPC UAUsage in Siemens SIMATIC ManagerHB300 | CPU | 013-CCF0R00 | en | 19-30192