5. Set in the register MPI the transfer parameters of your MPI net and type a validaddress.6. Switch to the register Local connection.7. Set the COM port of the PCs and the transfer rate 38400baud for the MPI program-ming cable from VIPA.8. Transfer your project via ‘PLC è Load to module’ via MPI to the CPU and save itwith ‘PLC è Copy RAM to ROM’ on a memory card if one is plugged.To switch the interface X3 MPI(PtP) to PROFIBUS functionality you haveto activate the according bus functionality by means of a VSC storagemedia from VIPA. By plugging the VSC storage card and then an overallreset the according functionality is activated.1. Connect your PC to the MPI(PtP) jack X3 of your CPU via a MPI programmingcable.2. Load your project in the Siemens SIMATIC Manager.3. Choose in the menu ‘Options è Set PG/PC interface’.4. Select in the according list the "PC Adapter (PROFIBUS)"; if appropriate you haveto add it first, then click at [Properties].5. Set in the register PROFIBUS the transfer parameters of your PROFIBUS net andenter a valid PROFIBUS address. The PROFIBUS address must be assigned to theDP master by a project before.6. Switch to the register Local connection.7. Set the COM port of the PCs and the transfer rate 38400baud for the MPI program-ming cable from VIPA.8. Transfer your project via ‘PLC è Load to module’ via PROFIBUS to the CPU andsave it with ‘PLC è Copy RAM to ROM’ on a memory card if one is plugged.Transfer via PROFIBUS is available by DP master, if projected as masterand assigned with a PROFIBUS address before. In slave operation youhave also to enable the option ‘Test , Commissioning, Routing ’ whenselecting the slave mode.4.10.2 Transfer via EthernetSo that you may access the according Ethernet interface you have to assign IP addressparameters by means of the "initialization".n X1/X2: Ethernet PG/OP channel–Ä Chap. 4.7 ‘Hardware configuration - Ethernet PG/OP channel’ page 721. For the transfer, connect, if not already done, the appropriate Ethernet port to yourEthernet.2. Open your project with the Siemens SIMATIC Manager.3. Set via ‘Options è Set PG/PC Interface’ the access path to "TCP/IP ® Networkcard .... ".Proceeding Transfer viaPROFIBUS interfaceInitializationTransferVIPA System SLIODeployment CPU 013-CCF0R00Project transfer > Transfer via EthernetHB300 | CPU | 013-CCF0R00 | en | 19-3092