11 Option: Deployment PROFIBUS communication11.1 Fast introductionThe PROFIBUS DP slave is to be configured in the hardware configurator from Siemens.Here the configuration happens by the sub module X1 (MPI/DP) of the Siemens CPU.To switch the interface X3 MPI(PtP) to PROFIBUS functionality you haveto activate the according bus functionality by means of a VSC storagemedia from VIPA. By plugging the VSC storage card and then an overallreset the according functionality is activated.Ä Chap. 4.16 ‘Deploymentstorage media - VSD, VSC’ page 111For the configuration of the PROFIBUS DP master please follow the following approach:n Enable bus functionality via VSCn Hardware configuration - CPUn Deployment as DP master or DP slave– With activating the bus function ‘PROFIBUS DP master’ by means of the VSC,the bus function ‘PROFIBUS DP slave’ is also unlocked.n Transfer of the complete project to CPUWith the Siemens SIMATIC Manager, the CPU 013-CCF0R00 from VIPAis to be configured asCPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3)The integrated PROFIBUS DP master (X3) is to be configured and con-nected via the sub module X1 (MPI/DP).OverviewSteps of configurationVIPA System SLIOOption: Deployment PROFIBUS communicationFast introductionHB300 | CPU | 013-CCF0R00 | en | 19-30254