Operating parameters Description AssignmentPeriod With the period you define the length of the outputsequence, which consists of pulse duration and pulsepause.Range of values:Time base 1ms: 1 ... 87msTime base 0.1ms: 0.4 ... 87.0ms50*Minimum pulse duration With the minimum pulse duration you can suppress shortoutput pulses and short pulse pauses. All pulses orpauses, which are smaller than the minimum pulse dura-tion, are suppressed. This allows you to filter very shortpulses (spikes), which can not be recognized by theperiphery.Range of values:Time base 1ms: 0 ... Period / 2 · 1msTime base 0.1ms: 2 ... Period / 2 · 0.1ms2*) This value can vary depending on the configuration tool and can be out of range. Values, which are out of range are invalid and must be adjusted accordingly!5.8.5 Status indicationDigital output LEDgreenDescriptionDO +0.0 PWM 0 has "1" signalPWM 0 has "0" signalDO +0.1 PWM 1 has "1" signalPWM 1 has "0" signalPower supply LEDgreenDescription1L+ DC 24V electronic section supply OKDC 24V electronic section supply not available2L+ DC 24V power section supply outputs OKDC 24V power section supply outputs not available3L+ DC 24V power section supply SLIO bus OKDC 24V power section supply SLIO bus not available5L+ DC 24V power section supply inputs OKDC 24V power section supply inputs not availableVIPA System SLIODeployment I/O peripheryPulse width modulation - PWM > Status indicationHB300 | CPU | 013-CCF0R00 | en | 19-30156