4.5 Hardware configuration - CPUn The configuration of the CPU takes place at the ‘hardware configurator’ of the Sie-mens SIMATIC Manager V 5.5 SP2 and up.n The configuration of the System SLIO CPU happens by means of a virtualPROFINET IO device ‘VIPA SLIO System’ . The ‘VIPA SLIO System’ is to beinstalled in the hardware catalog by means of the GSDML.For project engineering a thorough knowledge of the Siemens SIMATICManager and the Siemens hardware configurator is required!The installation of the PROFINET IO devices ‘VIPA SLIO System’ happens in the hard-ware catalog with the following approach:1. Go to the service area of www.vipa.com.2. Load from the download area at ‘Config files è PROFINET’ the according file foryour System SLIO.3. Extract the file into your working directory.4. Start the Siemens hardware configurator.5. Close all the projects.6. Select ‘Options è Install new GSD file’7. Navigate to your working directory and install the according GSDML file.ð After the installation according PROFINET IO device can be found at‘PROFINET IO è Additional field devices è I/O è VIPA SLIO System’In the Siemens SIMATIC Manager the following steps should be executed:1. Start the Siemens hardware configurator with a new project.2. Insert a profile rail from the hardware catalog.3. Place at ‘Slot’ -Number 2 the CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).4. Click at the sub module ‘PN-IO’ of the CPU.5. Select ‘Context menu è Insert PROFINET IO System’.PreconditionInstallation IO device‘VIPA SLIO System’ProceedingVIPA System SLIO Deployment CPU 013-CCF0R00Hardware configuration - CPUHB300 | CPU | 013-CCF0R00 | en | 19-30 69