Description of application and parametersApplication "RTC"Product manual 2CKA001473B9679 │10011.4.24 Control of additional heating stage — Additional heating typeOptions: PI continuous, 0 – 100% and PI PWM, On/Off:■ Area (e.g. floor heating) 4°C 200 min■ Convector (e.g. heater) 1.5°C 100 min■ Free configurationFan coil:■ Fan coil 4°C 90 min■ Free configurationMultiple heating types (panel heating, convector heating or fan coil) with preset parameters areavailable to the user.– If the required heating type is not available, individual parameters can be specified in thefree configuration.NoteThis parameter is only available when "Control value type" parameter for theadditional stage is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or"Fan coil".11.4.25 Control of additional heating stage — P-component (x 0.1°C)Options: Setting option between 10 - 100The P-component refers to the proportional range of a control. It fluctuates around the setpointvalue and can be used to influence control speed of a controller. The smaller the setpoint, thefaster the controller responds. However, to avoid the risk of an overshoot, this value should notbe set too low. A P-component from 0.1 to 25.5 K can be set.NoteThis parameter is only available when "Control value type" parameter for theadditional stage is set either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or"Fan coil". The "Additional heating type" parameter must be set on "Freeconfiguration".