Communication objectsCommunication objectsProduct manual 2CKA001473B9679 │35112.1.49 RTC - Request manual fan speed levelName Object function Data typeRTC: Request manual fan speedlevel(Master)Input 1.001 SwitchingRTC: Request manual fan speedlevel(Slave)Output 1.001 SwitchingThe communication object is used to transmit the request of the manual or automatic fan speedlevel control of a slave device to the master device. This means that value 0 "Automatic fanspeed level control", the value 1 "Manual fan speed level control"NoticeWhen the master/slave operation is activated, the object "RTC: Request manualfan speed level (master)" of the master device for synchronisation must beconnected with object "RTC: Request manual fan speed level (slave)" of theslave device.12.1.50 RTC - Request fan speed levelName Object function Data typeRTC: Request fan speed level(Master) Input 5.001 Percentage value6.010 Counter valueRTC: Request fan speed level(Slave) Output 5.001 Percentage value6.010 Counter valueThe communication object is used to transmit the request of a fan speed level via the buttonoperation of a slave device to the master device. The values can be transmitted as percentagevalues or counter values.NoticeWhen the master/slave operation is activated, the object "RTC: Request fanspeed level (master)" of the master device for synchronisation must beconnected with object "RTC: Request fan speed level (slave)" of the slavedevice.12.1.51 RTC - Confirm fan speed levelName Object function Data typeRTC: Confirm fan speed level(Master) Output 5.001 Percentage value6.010 Counter valueRTC: Confirm fan speed level(Slave) Input 5.001 Percentage value6.010 Counter valueThe communication object is used to transmit the fan speed level confirmation of the masterdevice to a slave device. The values can be transmitted as percentage values or countervalues.