Description of application and parametersApplication "CO2 sensor"Product manual 2CKA001473B9679 │16011.5.19 Settings — Value below threshold 1 (-255) for output format byteOptions: 0-255If the parameterised value of the threshold is undershot, a defined parameterised value is senton the KNX bus to reset the event that occurred beforehand. E.g. a fan is activated when thethreshold is undershot to supply the room with fresh air. When the change of air has occurredand the CO2 concentration has again dropped below the threshold value, the fan is switchedoff.NoticeThe parameter is available only when parameter "Control value output format" isset on "Byte".11.5.20 Settings — Value below threshold 1 (-64) for output format sceneOptions: 1-64If the parameterised value of the threshold is undershot, a defined parameterised value is senton the KNX bus to reset the event that occurred beforehand. For example, a fan is activatedwhen the threshold is undershot to supply the room with fresh air. When the change of air hasoccurred and the CO2 concentration has again dropped below the threshold value, the fan isswitched off.NoticeThe parameter is available only when parameter "Control value output format" isset on "Scene".