Communication objectsCommunication objectsProduct manual 2CKA001473B9679 │34012.1.24 RTC - Current setpointName Object function Data typeRTC: Current setpoint Output 9.001 Temperature valueThe communication object outputs the current setpoint temperature. The value results from theset setpoint temperature of the current operating mode, the manual setpoint temperatureadjustment and a change in the basic setpoint temperature via the "RTC: Basic set value".12.1.25 RTC - Normal operating modeName Object function Data typeRTC: Normal operating mode On 20.102 HVAC modeRTC: Normal operating mode(master) On 20.102 HVAC modeRTC: Normal operating mode(Slave) On 20.102 HVAC modeThe value for the switchover of the operating mode is received via the 1-byte communicationobject. Meaning of values:■ "1": Comfort■ "2": Standby■ "3": Economy■ "4": Building protectionIn addition to manual setpoint adjustment and the adjustment of the basic setpoint value, thesetpoint temperature of the controller is defined by the following communication objects (listedin decreasing order of priority):■ "RTC: Override operating mode"■ "RTC: Condensate water alarm"■ "RTC: Dew point alarm"■ "RTC: Window contact"■ "RTC: Control On/Off"■ "RTC: Presence detector"■ "RTC: Normal operating mode"NoticeWhen the master/slave operation is activated, the object "RTC: Normaloperating mode (master)" of the master device must be connected with object"RTC: Normal operating mode (slave)" of the slave device.